MODEL
NUMBER
RECOVERY RATE
GPH
INPUT
kW
ELEMENT AMPS
SHIPPING
WEIGHT
lbs
40°-120°F 40°-140°F
240V, 1Ø 208V, 3Ø 240V, 3Ø 480V, 3Ø
45 P 300A-E 45 37 9 38 25 22 11 1470
90 P 300A-E 90 70 18 75 50 44 22 1470
140 P 300A-E 140 111 27 113 75 65 33 1470
180 P 300A-E 180 150 36 150 100 87 44 1470
230 P 300A-E 230 184 45 188 125 109 55 1480
270 P 300A-E 270 220 54 225 150 130 65 1480
320 P 300A-E 320 256 63 263 175 152 76 1480
370 P 300A-E 370 300 72 300 200 174 87 1480
410 P 300A-E 410 330 81 338 225 195 98 1490
460 P 300A-E 460 370 90 375 250 217 109 1490
510 P 300A-E 510 400 99 413 275 239 120 1490
550 P 300A-E 550 440 108 450 300 260 130 1490
650 P 300A-E 650 515 126 525 350 304 152 1520
740 P 300A-E 740 590 144 600 400 347 174 1540
830 P 300A-E 830 660 162 675 450 390 195 1540
920 P 300A-E 920 740 180 750 500 434 217 1570
1100 P 300A-E 1100 880 216 900 600 520 260 1580
1300 P 300A-E 1300 1030 252 1050 700 607 304 1590
1470 P 300A-E 1470 1180 288 1200 800 693 347 1600
1650 P 300A-E 1650 1330 324 1350 900 780 390 1610
1850 P 300A-E 1850 1480 360 1500 1000 867 434 1620
DURAWATT
®
ELECTRIC • PACKAGED WATER HEATER
POLYSHIELD
®
POLYMER-LINED STORAGE TANK
STANDARD ELECTRICAL REQUIREMENTS:
CONTROL CIRCUIT TRANSFORMER SUPPLIED ON 480V ONLY. TAPPED CONTROL CIRCUIT INTERNALLY WIRED FOR 208V AND 240V.
208V AND 240V MODELS REQUIRE AC NEUTRAL CONDUCTOR FOR GROUNDING OF CONTROL CIRCUIT.
ALTERNATE VOLTAGES: FOR 230/460V, MULTIPLY kW AND RECOVERY BY .92. MULTIPLY AMPS BY .96.
FOR 220/440V, MULTIPLY kW AND RECOVERY BY .84. MULTIPLY AMPS BY .92.
TANK SERIES 300 GALLONS
ASHRAE 90.1 compliant.
For standard and optional equipment, see form #PV 6010.