Panasonic Electric Works Fire & Security Technology Europe AB
Jungmansgatan 12, SE-211 19 Malmö, Sweden
Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99
info-fste@eu.pewg.panasonic.com • www.panasonic-fire-security.com
Fire alarm systems
Enclosed
addressable manual
call point
3339
• Attractive design compliant with EN54-11. IP rating IP67
• Test key for routine testing without breaking the glass element
• Protection against accidental operation
General
The call point has an attractive design
compliant with EN54-11, and is surface
mounted in the supplied red backbox. It has
a clip retained front cover that makes it easy
to replace the glass element and adds
security since the clips are concealed. The
frangible element is a glass element with a
protective plastic film. To operate the call
point, the glass element is pressed until it is
broken. This will activate the built-in
microswitch, which will generate a fire
alarm in the c.i.e.
Test key
Routine testing is made with a supplied test
key, without breaking the glass element.
Inserting the test key simulates the breaking
of the glass element. The call point is
automatically reset when the test key is
removed. The test key is also used to
release the security clips for the front cover.
Protective cover
To protect the call point against accidental
operation, a transparent polycarbonate cover
has to be lifted to get access to the glass
element.
Encapsulated circuit
All electronics are encapsulated. Only the
terminal block is accessible from the rear.
Mounted in the supplied red backbox and
the tightening gasket on place (see the
opposite page), the IP rating is IP67.
LED indicator
An LED on the front cover indicates fire
alarm generated by the call point.
Flashing LED: The LED will flash each
time the c.i.e. communicates with the call
point, until the call point is operated and the
LED is switched on.
Non-flashing LED: The LED is switched
off until the call point is operated and the
LED is switched on.
Connections / Settings
The COM loop is connected directly to the
call point via a 4-way terminal block. For
COM loop address setting is the address
setting tool 3314 used. 3314 is also used to
set the call point type and the LED mode:
• NORMAL mode: (EBL512 SW
version >
2.0 / EBL128). M.c.p. type
3339. (Flashing or non-flashing LED is
set via Win512 / Win128.)
• 2330 mode: M.c.p. type 2339
, flashing
LED.
• 2312 mode: M.c.p. type 2339
, non-
flashing LED.
Two flying leads (wires) are connected to
the terminal block, for connection of the
3314 address setting tool's connection cable.
The wires are to be disconnected before the
COM loop wires are connected.
Product applications
Used in the systems EBL512 / 128 / 1000 /
2000 and is intended for indoor use in
premises where IP67 rating is required.