Monessen Hearth CSDV40NDV Stove User Manual


 
22
58D6056
CSDV Series Direct Vent Gas Stove


Use proper gas type for the fireplace you are installing. If you have conflicting gas type, do not install
fireplace. See dealer where you purchased the fireplace for proper fireplace according to your gas
type.

When using copper or flex connectors use only fittings
approved for gas connections. The gas control inlet is
3/8" NPT.


   

    
    
     




Before installing stove and burner system, make sure you have the items listed below.
External regulator Piping (check local codes) Sealant (resistant to propane/LP gas)
(supplied by installer) Test gauge connection* • Sediment trap (recommended)
Equipment shutoff valve* Tee joint Pipe wrench
approved flexible gas line with gas connector (if allowed by local codes — not provided)
* A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge con-
nection. Purchase the CSA design-certified equipment shutoff valve from your dealer.
For propane/LP connections only, the installer must supply an external regulator. The external regulator will reduce
incoming gas pressure. You must reduce incoming gas pressure to between 11 and 13 inches of water. If you do not
reduce incoming gas pressure, burner system regulator damage could occur. Install external regulator with the vent
pointing down as shown in Figure 32. Pointing the vent down protects it from freezing rain or sleet.
       
   






      


    


 
FP1977
external regulator
External
Regulator
100 gal. (min)
Propane/LP
Supply Tank
Vent Pointing
Down
Figure 32 -
External Regulator with Vent Pointing Down
(Propane/LP Only)
FP1977