Monessen Hearth C2801VF Stove User Manual


 
8 45D0080
45D0080 9
The following formula can be used to determine the maximum heater rating per the denition of unconned space:
BTU/Hr = (L1 + L2) Ft x (W) Ft x (H) Ft
50
Consider two connecting rooms with an open area between, with the following dimensions:
L1 = 15
1
/2 Ft., L2 = 12 Ft., W = 12 Ft., H = 8 Ft.
BTU/Hr = (15
1
/2 + 12) x (12) x (8)
50
If there were a door between the two rooms the calculation would be based only on the room with the heater.
BTU/Hr = (15
1
/2) x (12) x (8)
50
Figure 2 - Example of a Large Room with 1/2 Wall Divider
Counter
Cast Iron Stove
x 1000
x 1000 = 52800 BTU/Hr
x 1000 = 29760 BTU/Hr
If the area in which the heater may be operated is smaller than that defined as an
unconfined space or if the building is of unusually tight construction, provide adequate
combustion and ventilation air by one of the methods described in the National Fuel
Gas Code, ANSI Z223.1, NFPA54, Section 5.3 or applicable local codes.