Mitsubishi Electronics Q173HCPU Home Security System User Manual


 
2 - 46
2 MULTIPLE CPU SYSTEM
Table 2.4 Multiple CPU errors which occurs in the Motion CPU (1000 to 10000)
Occurs CPU LED status
Middle
classification
Error messages
Error
code
Error information
Classification code
Single
composition
Multiple
composition
RUN ERROR
Operating
status of CPU
Diagnostic
timing
1000
1001
1002
1003
1004
1005
1006
1007
1008
MAIN CPU DOWN
1009
— — OFF Flickers Stop Always
In the CPU,
RAM error
(RAM ERROR)
1105 —
OFF Flickers Stop
At power supply
ON/at reset
CPU (hard)
error
FUSE BREAK OFF 1300 OFF/ON Flickers/ON
Stop/Continue
(Note-7)
Always
Module
error (hard)
SP. UNIT DOWN 1401 Module No.
OFF Flickers Stop
At power supply
ON/at reset
1413 Module No.
OFF Flickers Stop Always
1414 Module No.
OFF Flickers Stop Always
1415 Base No.
(Note-2)
OFF Flickers Stop Always
Base
Q bus error
(CONTROL-BUS
ERROR)
1416 Module No.
(Note-1)
OFF Flickers Stop
At power supply
ON/at reset
Power
supply
Detection of AC/DC
DOWN (AC/DC DOWN)
1500 —
ON OFF Continue Always
1600 ON OFF
Battery (BATTERY ERROR)
1601
Drive name
BAT. ALM
LED ON
Continue Always
2121
2124
2125
Module No.
Handling the
intelligent
function
module/
Multiple
CPU
module
Intelligent function
module installation error
(SP. UNIT LAY
ERROR)
2126 Module No.
(Note-1)
OFF Flickers Stop
At power supply
ON/at reset
(Note-1) : CPU No. is stored in slot No. of the common information classification.
(Note-2) : Base No. in "common information classification code" of "error information classification code" is 0 : CPU base, 1 to 7 : Number of extension bases.
(Note-3) : Because a stop error or CPU No. except CPU No. that it was reset becomes MULTI CPU DOWN simultaneously, a stop error or CPU No. except CPU
No. that it was reset may store in the classification of error information depending on timing.
(Note-4) : When an error occurs in the Motion CPU and so on except PLC CPU, if a PC diagnosis is made in the CPU except PLC CPU from GX Developer via
PLC CPU, the error code "10000" is indicated.
(Note-5) : The Motion SFC error detection signal (M2039) turned on at the error detection (SV13/SV22). A self-diagnosis error flag (M9008) and a diagnosis error
flag (M9010) do not turn on at the error detection. The error code "10000" being set in D9008 is reset in the Motion SFC error detection signal (M2039)
ON
OFF (SV13/SV22).
(Note-6) : MOTION RUN LED turns off at the stop error occurrence. (The condition of RUN LED does not change.)
(Note-7) : Operating status of CPU at the error occurrence can be set in the parameter. (LED display also changes continuously.)