Job Name: Location: Date:
Purchaser: Engineer:
Submitted to: For Reference Approval Construction
Unit Designation: Schedule No.:
Cooling*
Rated Capacity...............................24,000 Btu/h
Minimum Capacity ............................12,000 Btu/h
SEER ......................................16.8 Btu/h/W
EER ...................................... 10.3 Btu/h/W
Total Input......................................2,340 W
* Rating Conditions (Cooling) - Indoor: 80ºF (27ºC) DB / 67ºF (19ºC) WB.
Outdoor: 95ºF (35ºC) DB / 75ºF (24ºC) WB.
Electrical Requirements
Power Supply ....................208 / 230V, 1-Phase, 60 Hz
Recommended Fuse/Breaker Size.......................25 A
Voltage
Indoor - Outdoor S1-S2 ......................AC 208 / 230V
Indoor - Outdoor S2-S3 ............................DC 24V
OPERATING CONDITIONS
Indoor Intake Air Temp. Outdoor Intake Air Temp.
Cooling
Maximum 95ºF (35ºC) DB, 71ºF (22ºC) WB 115ºF (46ºC) DB
Minimum 67ºF (19ºC) DB, 57ºF (14ºC) WB 0ºF** (-18ºC) DB
** With optional wind bafe accessory installed. If not installed, the minimum
temperature will be 23ºF (-5ºC) DB.
Indoor Unit: PCA-A24KA4
Outdoor Unit: PUY-A24NHA4
Indoor Unit
MCA .............................................. 1 A
Fan Motor ...................................0.54 F.L.A.
Fan Motor Output ...................................95 W
Airow (Lo - Mid1 - Mid2 - Hi)..... 530 - 565 - 600 - 670 Dry CFM
495 - 530 - 565 - 635 Wet CFM
Air Filter ........................ Polypropylene Honeycomb
Sound Pressure Level (Lo - Mid1 - Mid2 - Hi).........33 - 35 - 37 - 40 dB(A)
SHF ............................................. 0.73
Moisture Removal................................ 5.8 pt./h
DIMENSIONS UNIT INCHES / MM
W 50-3/8 / 1,280
D 26-3/4 / 680
H 9-1/16 / 230
Weight. ....................................71 lbs. / 32 kg
External Finish ....................Munsell No. 6.4Y 8.9 / 0.4
Field Drainpipe Size O.D.....................1-1/16" / 26 mm
Outdoor Unit
Compressor ..................DC Inverter-driven Twin Rotary
MCA ............................................ . 18 A
MOCP............................................ 30 A
Fan Motor ....................................0.75 F.L.A.
Sound Pressure Level
Cooling .................................... . .48 dB(A)
DIMENSIONS INCHES / MM
W 37-3/8 / 950
D 13 + 1-3/16 / 330 + 30
H 37-1/8 / 943
Weight ...................................163 lbs. / 74 kg
External Finish ......................Munsell No. 3Y 7.8/ 1.1
Refrigerant Type.................................. R410A
Refrigerant Pipe Size O.D.
Gas Side ................................5/8" / 15.88 mm
Liquid Side................................3/8" / 9.52 mm
Max. Refrigerant Pipe Length.....................165' / 50 m
Max. Refrigerant Pipe Height Difference ............100' / 30 m
Connection Method ................................Flared
SUBMITTAL DATA: PCA-A24KA4 & PUY-A24NHA4. . . . . . . . . . . . . . 24,000 BTU/H CEILING-SUSPENDED AIR-CONDITIONING SYSTEM
GENERAL FEATURES
• Ceiling-suspended indoor unit for residential and commercial
applications
• Shiny white cabinet; compact design
• Standard air lter is included with indoor unit; high-efciency
lter is available as an option
• Setback down to 50°F when used with MRCH1 Central Controller
• Quiet operation—both indoor and outdoor units
• Self-check function—integrated diagnostics
• Limited warranty: ve years on parts and defects and seven years
on compressors
OPTIONAL ACCESSORIES
Indoor Unit
□ Mini Condensate Pump (PAC-SH84DM, 230V)
□ High-efciency Filter (PAC-SH89KF)
□ i-see Sensor with Mount (PAC-SH91MK-E)
Outdoor Unit
□ Drain Pan (PAC-SG64DP)
□ Drain Socket (PAC-SG61DS)
□ Three-pole Disconnect Switch (TAZ-MS303)
□ Wind Bafe (WB-PA2)
□ Air Outlet Guide (PAC-SG59SG)
□ Mounting Base (DSD-400N)
□ Mounting Pad (ULTRILITE2)
□ Wall-mounting Brackets (CWMB1)
Controller Options
□ Wireless Remote Controller Kit (MHK1) with Wall-mounted Central
Controller (MRCH1), Wireless Receiver (MIFH1), and cable*
□ Wall-mounted Central Controller (MRCH1)*
□ Wireless Receiver (MIFH1)*
□ Portable Central Controller (MCCH1; for use with Wireless Remote
Controller Kit MHK1)*
□ Outdoor Air Sensor (MOS1; for use with Central Controller (MRCH1),
Wireless Remote Controller Kit (MHK1) and Portable Central
Controller (MCCH1)*
*See Submittal for information on each option.
□ Wall-mounted Wired Remote Controller (PAR-21MAA)
□ M-NET Adapter (PAC-SF81MA)
□ CN51 Connector for Multiple Remote Controller Adapters/Duct Fan
Controller (PAC-725AD)
□ CN32 Connector for Remote On/Off (PAC-715AD)
□ Remote Temperature Sensor (PAC-SE41TS)
□ Remote Operation Adapter - Display and On/Off (PAC-SF40RM)
□ Wireless Remote Controller Kit (PAR-SL93B)
□ i-See Sensor and Wireless Remote Controller Kit (PAR-SA92MW)
□ Lockdown Bracket for Handheld Controller (RCMKP1CB)
□ Control/Service Tool (PAC-SK52ST)