LST IR2 16581 Smoke Alarm User Manual


 
0832–CPD–0821
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
IR2-16581_DBL_LST_EN_0850.PDF • PAGE 1
ABuilding Safety. Building Security.
Flame Detector IR
2
16581
Dual infrared sensor
according to EN 54-10, Class 1
Detection of open fl ames through
ickering infrared radiation
High immunity to deceptive alarms
Selectable response delay
Relay contacts for alarm and fault
Integrated optical test function
Description
The Flame Detector 16581 responds to the fl ickering
infrared radiation of open fl ames. Therefore, it is extre-
mely well suitable for the detection of fi res which are
diffi cult to detect with common smoke detectors – for
example, alcoholic fi res or gas fl ames.
The detector is ideal for the following applications:
• Aviation and automotive industry
• Paint shops
• Warehouses
• Textile industry
• Waste treatment
With two independent infrared sensors for different
wavelengths and with an intelligent evaluation logic, the
detector can safely distinguish between alarm situati-
ons and deceptive alarms. Therefore, it is very insensiti-
ve to disturbance sources such as sunlight, fl uorescent
lamps or electric arcs.
The detector complies with EN 54-10, Class 1, which
means it is suitable to detect fl ames up to a distance
of 25m.
The response delay of the detector can be selected in
4 steps between 1 and 8s. An alarm and a fault conditi-
on is signalled via two dry relay contacts. Conventional
technology is used for alarm transmission to the fi re
detection control panel. The detector can be integra-
ted into an ADM loop by means of a conventional zone
module.
A simple test of the detector can be carried out by
means of the integrated optical self test function, which
does not require additional tools. During this self test,
a built-in infrared source simulates a fi re situation which
activates the detector.
The detector has been designed for indoor use. The op-
tional Detector Mounting Bracket 7127 allows stepless
horizontal and vertical adjustment for the easy adaptati-
on of the detector to the required monitoring area.
For use in explosion-hazardous areas, an Ex version of
the fl ame detector is available on request.