LST IBSST-DR-P02 Smoke Alarm User Manual


 
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
IBSST-DR-P0x_DBL_LST_EN_0804.PDF • PAGE 1
ABuilding Safety. Building Security.
Sounder/Strobe
IBSST-DR-P01, IBSST-DR-P02
Description
ADM loop technology with
System Sensor/200 protocol
Can be activated with two different
tone types, 32 tone types selectable
Sound level selectable in three steps
– up to 95dB(A)
Low power consumption
Versions with or without integrated
dual-isolator available
Two base types available – IP24, IP44
Specifi cations
Operating voltage Supply through loop voltage
Sound level (detector installed) typ. 70dB(A) at 1m distance (low)
typ. 79dB(A) at 1m distance (medium)
typ. 87dB(A) at 1m distance (high)
max. 95dB(A) at 1m distance (high)
Flash frequency 1Hz
Ambient temperature -25°C to +70°C
Dimensions ø × H 112 × 42 (mm) (without detector, incl. base LPBW)
Weight 136g
Colour red / cream, RAL 9001
The loop powered sounder with strobe is fi tted into a
round, red plastic case. It is powered and actuated as
a module via the ADM loop with System Sensor/200
protocol. Fire Detectors Series 200 can be fi tted into
the integrated base.
The sounder can be activated by a Fire Detection Con-
trol Panel Series BC216 with two different tone types,
depending on the parameter setup. One of 32 different
tone type combinations can be selected with a DIL-
switch. The following tones are available, for example:
• Continuous tone 660Hz,
• Emergency signal according to DIN 33404,
• Slow whoop tone according to NEN 2575,
• Alternating tone 800/970Hz, and many more.
The sound level can be selected in 3 steps. The stro-
be is always activated together with the sounder. The
address of the sounder/strobe is selected with two
decadic rotary switches located at the bottom of the
device.
The device is designed for indoor surface mounting.
For this purpose a special base is needed. Two diffe-
rent base types for protection classes IP24 or IP44
are available, depending on the application. An optional
mounting plate can be supplied for surface mounted
cabling.
The sounder/strobe is available in two different versi-
ons: With or without integrated dual-isolator module.