LST IBSOU-DD-P01 Smoke Alarm User Manual


 
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
IBSOU-DD-P0x_DBL_LST_EN_0804.PDF • PAGE 1
ABuilding Safety. Building Security.
Integrated Base Sounder
IBSOU-DD-P01, IBSOU-DD-P02
Description
ADM loop technology with
System Sensor/200 protocol
Can be activated with two different
tone types, 32 tone types selectable
Sound level selectable in three steps
– up to 95dB(A)
Low power consumption
Versions with or without integrated
dual-isolator available
Two base types available – IP24, IP44
Specifi cations
Operating voltage Supply through loop voltage
Sound level (detector installed) typ. 70dB(A) at 1m distance (low)
typ. 79dB(A) at 1m distance (medium)
typ. 87dB(A) at 1m distance (high)
max. 95dB(A) at 1m distance (high)
Ambient temperature -25°C to +70°C
Dimensions ø × H 112 × 42 (mm) (without detector, incl. base LPBW)
Weight 134g
Colour cream, RAL 9001
The loop powered sounder incorporates a detector
base and is fi tted into a round, white plastic case. It is
powered and actuated as a module through the ADM
loop with System Sensor/200 protocol. Fire Detectors
Series 200 can be fi tted into the integrated base.
The sounder can be activated by a Fire Detection Con-
trol Panel Series BC216 with two different tone types,
depending on the parameter setup. One of 32 different
tone type combinations can be selected with a DIL-
switch. The following tones are available, for example:
• Continuous tone 660Hz,
• Emergency signal according to DIN 33404,
• Slow whoop tone according to NEN 2575,
• Alternating tone 800/970Hz, and many more.
The sound level can be selected in 3 steps. The address
of the sounder is selected with two decadic rotary swit-
ches located at the bottom of the device.
The base sounder is designed for indoor surface moun-
ting. For this purpose a special base is needed. Two
different base types for protection classes IP24 or IP44
are available, depending on the application. An optional
mounting plate can be supplied for surface mounted
cabling.
The sounder is available in two different versions: With