Thermal ROR Detector
FC600/TDIFF/57
Addressable conventional technology
Individual detector identifi cation with
optional address module
Maximum temperature 57°C
Allows for the connection of an
external remote indicator
Anti-tamper locking feature on
detector base
Function check by means of test
magnet
Description
Specifi cations
The Thermal Rate-of-Rise Detector FC600/TDIFF/57
will respond to temperatures above 57°C (EN 54 -5
class A1R) or an abrupt rise in temperature. It can be
used in rooms with a height of up to 7.5m. Any alarm
will be transmitted to the fi re detection panel in con-
ventional technology. An individual detector identifi ca-
tion can be obtained with the optional Address Module
NG58-1.
The detector is equipped with an LED indicator which
is visible from all sides at any angle and thus facilitates
easy identifi cation of the alarming detector. In addition,
a remote indicator can also be connected.
Several types of detector bases are available to faci-
litate quick and easy installation. To prevent unautho-
rized removal of the detector, all detector bases are
equipped with an anti-tamper locking feature. A de-
tector function test can be conveniently conducted by
using a test magnet.
Operating voltage 10 – 30VDC (supply through detector line voltage)
Current consumption typ. 40µA (normal condition)
Alarm temperature 57°C (maximum-heat component)
Operating temperature max. +45°C
Ambient temperature -30°C to +70°C
Relative humidity max. 95% (no condensation)
Dimensions ø × h (without base) 106 × 46 (mm)
Colour white
Weight 80g
Approvals LPCB 603b/02
0832-CPD-0127
Order number 242070
Order name Thermal ROR Detector/Conv./FC600 FC600/TDIFF/57