Strobes
55000-877, 55000-878, 55000-879
ADM loop technology with Apollo/
Discovery protocol
Suitable for surface mounting in the
detector base
Low power consumption
Long lifetime of strobe due to the use
of LEDs
Protective housing IP67 available as
accessory
Operating voltage Supply through loop voltage
Current consumption typ. 150µA (quiescent), 3mA (active)
Ambient temperature -10°C to +60°C
Protection class IP42
Dimensions ø × H 100 × 52 (mm)
Weight 85g
Red cap
Order number 356020
Order name Strobe/FB/XP95/White/Red 55000-877
Colourless cap, red LEDs
Order number 356022
Order name Strobe/FB/XP95/White/Clear 55000-878
Orange cap
Order number 356023
Order name Strobe/FB/XP95/White/Orange 55000-879
Description
The addressable, loop powered Strobes
• 55000-877 with red cap
• 55000-878 with colourless cap and red LEDs
• 55000-879 with orange cap
are accommodated in a round, white plastic case and
are fi tted into a Standard or Isolator Detector Base Se-
ries XP95. They are powered and actuated as modules
via the ADM loop with Apollo/Discovery protocol, and
they are designed for indoor use. Due to the use of
LEDs a very long lifetime distinguishes the strobes.
Specifi cations