LST 5451EIS Smoke Alarm User Manual


 
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
5451EIS_DBL_LST_EN_0804.PDF • PAGE 1
ABuilding Safety. Building Security.
IS Thermal ROR Detector
5451EIS for Hazardous Areas
Description
The Intrinsically Safe Thermal ROR Detector 5451EIS
uses the rate-of-rise heat detection principle and was
developed for the fi re detection in hazardous areas.
The detector, which is a combined maximum/rate-of-
rise heat detector, is assigned to class A1R and can be
used up to a maximum room height of 7.5m.
Conventional technology is used for alarm transmission
to the fi re detection control panel. In conjunction with
the Safety Barrier ES58-2, the detector reaches the
given Ex classifi cation. The two LEDs with 360° visibility
indicate the activated condition of the detector.
A detector function test can be conveniently conducted
using a magnet or a detector test device. The detector
can be attached to various bases and it can be protec-
ted against theft.
Conventional technology
Maximum temperature 60°C
Up to 20 detectors can be connected
to one safety barrier
Function testable with magnet
ATEX certifi ed
Specifi cations
Ignition protection intrinsically safe
Ex classifi cation EEx ia IIB T5
Current consumption typ. 100µA (quiescent)
Alarm temperature 60°C (maximum-heat component)
Ambient temperature -10°C to +43°C (continuous operation)
Relative humidity 10 – 93% (no condensation)
Dimensions ø × H 104 × 54 (mm)
Colour cream
Weight 80g
Approval BASEEFA03ATEX0155X
VdS G296050
Order number 242015
Order name IS Thermal ROR Detector/Conv./400/SS 5451EIS