ABuilding Safety. Building Security.
Thermal Max Detector
5351TE
• Addressable conventional technology
• Alarm temperature 58°C
• Addressing by means of address
module or detector parameterisation
• Remote readout of detector condition
• Function testable with Remote Test
Unit ECO1000RTU
Description
The Thermal Max Detector 5351TE recognises a ma-
ximum temperature of 58°C as sign of fi re. It complies
with Class A2S and can be used up to a room height
of 6m.
Addressable conventional technology is used for alarm
transmission to the fi re detection control panel. The
detector addressing can be achieved in 2 ways:
• A detector with an Address Module NG58-1 can be
individually identifi ed by the suitable control panel.
• An address, which has been stored in the detector
by means of the Remote Programming and Test Unit,
is displayed on the Zonal Display Unit S300ZDU.
A test activation of the detector can be carried out
using the Remote Test Unit ECO1000RTU. In addition
to the test activation of the detector, the Remote Pro-
gramming and Test Unit S300RPTU can also be used
to set and display the following detector parameters:
• the detector address, and
• the date of the previous maintenance.
The detector can be attached to various types of ba-
ses and it can be protected against theft.
Specifi cations
Operating voltage Supply through the detector line voltage
Current consumption typ. 85µA (quiescent)
Alarm temperature 58°C
Operating temperature max. +45°C
Ambient temperature -30°C to +70°C (continuous operation)
Relative humidity 5 – 95% (no condensation)
Dimensions ø × H 102 × 43 (mm)
Colour cream
Weight 75g
Approval LPCB 199n Issue9
Order number 242042
Order name Thermal Max Detector/Conv./300/SS 5351TE