© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
1151EIS_DBL_LST_EN_0804.PDF • PAGE 1
ABuilding Safety. Building Security.
IS Ionisation Smoke Detector
1151EIS for Hazardous Areas
Description
Specifi cations
The Intrinsically Safe Ionisation Smoke Detector
1151EIS was developed for the safe detection of a
wide range of smoke aerosols. The modern design of
the ionisation chamber allows to reliably evaluate the
characteristics of fi re.
Conventional technology is used for alarm transmission
to the fi re detection control panel. In conjunction with
the Safety Barrier ES58-2, the detector reaches the
given Ex classifi cation. The two LEDs with 360° visibility
indicate the activated condition of the detector.
A detector function test can be conveniently conducted
using a magnet or test gas. The detector can be at-
tached to various bases and it can be protected against
theft.
• Conventional technology
• Up to 20 detectors can be connected
to one safety barrier
• Extremely fl at design
• Function testable with magnet
• ATEX certifi ed
Ignition protection intrinsically safe
Ex classifi cation EEx ia IIB T5
Current consumption at 24V typ. 40µA (quiescent)
Ambient temperature 0°C to +50°C
Relative humidity 10 – 93% (no condensation)
Radioactive compound Am241, 0.5µCi (18.5kBq)
Dimensions ø × H 103 × 42 (mm)
Colour cream
Weight 104g
Approval BASEEFA03ATEX0156X
VdS G296051
Order number 240015
Order name IS Ionisation Smoke Detector/Conv./100/SS 1151EIS