Lochinvar KB-500 Boiler User Manual


 
KB-399 KB-500 KB-600 KB-700 KB-800
WATER
GALLON CAPACITY 3.4 4.2 4.2 5.0 5.7
HEATING SURFACE (SQ. FT.) 41.8 50.8 50.8 57.8 65.3
WATER CONNECTIONS 1-1/2” 1-1/2” 2" 2" 2"
DRAIN 3/4” 3/4” 3/4" 3/4" 3/4"
20°F ΔT WATER FLOW (GPM) 37 47 55 65 74
HEAD LOSS (FT. OF HD.) 21 23 31 30 33
35°F ΔT WATER FLOW (GPM) 21 26 32 37 42
HEAD LOSS (FT. OF HD.) 8 10 13 11 12
MAX. WORKING PRESSURE (PSI) 160 160 160 160 160
# OF RELIEF VALVES 11111
RELIEF VALVE SIZE 3/4” 3/4” 3/4" 3/4" 3/4"
RELIEF VALVE RATING (MBH) 697 697 697 1,352 1,352
RELIEF VALVE PRESSURE RATING (PSI) 50 50 50 50 50
GAS
INLET CONNECTION 1” 1” 1" 1" 1"
MAX. INLET PRESSURE, NAT 10.5” w.c. 10.5” w.c. 10.5” w.c. 10.5” w.c. 10.5” w.c.
MIN. INLET PRESSURE, NAT 4.0” w.c. 4.0” w.c. 4.0” w.c. 4.0” w.c. 4.0” w.c.
MAX. INLET PRESSURE, LP 13.0” w.c. 13.0” w.c. 13.0” w.c. 13.0” w.c. 13.0” w.c.
MIN. INLET PRESSURE, LP 8.0” w.c. 8.0” w.c. 8.0” w.c. 8.0” w.c. 8.0” w.c.
BTU/HR INPUT 399,000 500,000 600,000 700,000 800,000
BTU/HR OUTPUT (HIGH FIRE) 372,267 466,500 567,600 660,100 752,000
BTU/HR OUTPUT (LOW FIRE) 74,453 93,300 113,520 132,020 150,400
ELECTRICAL
VOLTAGE/HEATER 120 120 120 120 120
VOLTAGE/CONTROL 24 24 24 24 24
TOTAL AMPS 1.5 1.7 2.7 2.7 2.7
# OF ELECTRICAL CONNECTIONS 11111
DIMENSIONS
HEIGHT 42-1/2” 42-1/2” 42-1/2" 42-1/2” 42-1/2”
WIDTH 15-1/2” 15-1/2” 15-1/2" 15-1/2" 15-1/2"
DEPTH 27” 31-1/4” 36-1/4" 40-1/4" 45-1/4"
SERVICE CLEARANCES
FRONT 24” 24” 24” 24” 24”
BACK 14” 14” 14” 14” 14”
RIGHT SIDE 0” 0” 0” 0” 0”
LEFT SIDE (PIPING) 24” 24” 24” 24” 24”
TOP 24” 24” 24” 24” 24”
DIRECT VENTING
SIZE 4” 4” 4" 6" 6"
VENT CATEGORY IV IV IV IV IV
VENT MATERIAL PVC PVC PVC PVC PVC
KBX-PS-03 (Replaces KBX-PS-02 06/08)
06/08-Printed in U.S.A.
Lochinvar Corporation • 300 Maddox Simpson Pkwy • Lebanon, TN 37090 • 615-889-8900 / Fax: 615-547-1000
www.Lochinvar.com
KNIGHT
®
BOILER PRODUCT SUMMARY
(KB) 399,000 - 800,000 BTU/HR