Lightolier LWL2 Indoor Furnishings User Manual


 
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
www.lightolier.com © 2008 Philips Group • C0308
Job Information Type:
Job Name:
Cat. No.:
Lamp(s):
Notes:
LWL2 Series Wet/Damp Location Exit LWL 2
Page 1 of 1
Lightolier is a Philips group brand
Features
1. Illumination: Illumination of the exit face is accomplished with long
lasting, high output Light Emitting Diodes (LEDs). Hot spots and striations are
eliminated by the internal light chamber, which is specially designed around
the high performance LED array. Average illumination levels are in excess of
25 fl (79 cd/M2).
2. Housing: Constructed of die cast aluminum with premium impact-resistant
injection molded polycarbonate covers. Housing is powder coated and back
cover is molded in color to match. Front cover is clear. Stencil is stamped
aluminum with field selectable chevrons and is contained inside the fully
gasketed housing for corrosion protection. Universal knockouts on backplate
allow wall mounting directly to standard junction boxes. Die cast aluminum
canopy is provided for top/side mounting and is powder coated to match
housing.
3. Electronics: AC Only or Emergency Operation.120/277 dual voltage input.
Emergency Operation version utilizes solid-state circuitry, and it’s charging
system is complete with low voltage disconnect, AC lockout, brownout
protection, AC indicator lamp and test switch.
4. Self-Diagnostics/Self-Testing: Standard on self-powered models, self-
testing mode automatically runs a one minute test every 30 days and a 30
minute test every 180 days. A one minute or 90 minute test may be initiated
via the push to test switch on the unit or by activating the appropriate test
command on the SDREMOTE test device accessory.
5. Input Power Requirements: AC Only — Red: 3.8 watts (120 VAC),
PF=0.96, 3.8 watts (277 VAC), PF=0.91; Green: 4.0 watts (120 VAC), PF= 0.95,
4.0 watts (277 VAC), PF=0.90
Self-Powered — Red: 4.7 watts (120 VAC), PF=0.95, 4.8 watts (277 VAC),
PF=0.97; Green: 4.7 watts (120 VAC), PF= 0.95, 4.7 watts (277 VAC), PF=0.99
6. Battery: Maintenance free, sealed nickel cadmium battery has an estimated
service life of 10 years, and an operating temperature range of -40°F (-40°C)
to 113°F (45°C). .
7. Warranty: Electronics: 5 years; Battery: 5 years full, 5 years pro-rata
Options
A = Self-Diagnostics with audible alarm
BF = Buzzer/Flasher (Emergency units only)
BZ = DC Buzzer
EX = Special Input Transformer (consult factory)
FA = 24 VDC Fire Alarm Interface
FL = Emergency Flasher (Emergency units only)
SW = Special Wording (Consult factory)
PM = Knock-out only for pendant mounting. Pendant kit must be ordered separately.
2CKT1 = 120 VAC Two Circuit
2CKT2 = 277 VAC Two Circuit
Accessories
T15TPTOOL = Tamperproof Screwdriver
SDREMOTE = Infrared Test Device
TPKITB = Pendant Kit w/ 12” Stem, Black (Consult factory for longer lengths)
TPKITW = Pendant Kit w/ 12” Stem, White (Consult factory for longer lengths)
Vandal-Resistant LED Exit Suitable for Wet or Damp Locations and Harsh Environments
The LWL2 Series is a harsh environment LED Exit suitable for use in wet or damp location areas. It offers rugged construction along with appealing aesthetics. High
performance electronics ensure long lasting reliability even in the most severe environments. Self Diagnostics/Self Testing is standard on self-powered models.
13.88”
(35.26 cm)
How to Specify:
SERIES BATTERY FACE LETTER STENCIL FACE/ STANDARD FEATURE
OPTIONS COLOR HOUSING COLOR
LWL2 = LWL2 Series Wet/Damp N = Nickel Cadmium 1 = Single R = Red W = White Housing and White Stencil SD2T = Self-Diagnostics/
Location LED Exits A = AC Only U = Universal G = Green B = Black Housing and Black Stencil Self-Testing
1
Single/Double G = Gray Housing and Gray Stencil
Face WA = White Housing / Brushed Aluminum Stencil
BA = Black Housing / Brushed Aluminum Stencil
GA = Gray Housing / Brushed Aluminum Stencil
LWL2
5.25”
(13.3 cm)
4.5”
(11.4 cm)
2.4”
(6.1 cm)
8.85”
(22.48 cm)
10.0”
(25.4 cm)
Notes: 1) Nickel cadmium units only