Lightolier DE Series Indoor Furnishings User Manual


 
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
www.lightolier.com © 2008 Philips Group • F0308
Job Information Type:
Job Name:
Cat. No.:
Lamp(s):
Notes:
DE Series Emergency Lighting Fixtures DE
Page 1 of 1 Combustible Dust Emergency Lighting Fixture
Lightolier is a Philips group brand
The DE Series is designed for remote and unit equipment mounting applications where suspended metal carbon and grain dust create an explosive or ignitable
atmosphere. The DE Series is UL listed for use in Class II, Divisions 1 & 2, Groups E, F & G, and Class III areas.
How to Specify:
9.75”
24.8 cm
4.19”
10.6 cm
5.38”
13.7 cm
DESC
5.38”
13.7 cm
16.38”
41.6 cm
6.00”
15.2 cm
DEEM
5.38”
13.7 cm
8.38”
21.3 cm
16.38”
41.6 cm
DESW
DEDW
21.0”
(53.3 cm)
20.0”
(50.8 cm)
8.0”
(20.3 cm)
DE
SERIES FIXTURE VOLTAGE
TYPE
DE = Combustible
Dust Emergency
Lighting Fixture
SC = Ceiling Mount
EM = End Mount
SW = Single Wall Remote
DW = Double Wall Remote
1 = 6 VDC, 12W
2
2 = 12 VDC, 12W
2
3 = 120 VAC
1
NOTES:
1) 120 VAC incandescent
lamps are not included.
Maximum wattage is 200
watts.
2) Emergency heads utilize
a 12 watt halogen lamp,
included.
Features
1. Illumination: Illumination is accomplished with halogen or incandescent
lamps that are adjustable to 360°.
2. Housing: Constructed of corrosion-resistant, cast aluminum alloy with an
epoxy polyester finish. Ceiling mount fixture and single wall remote have uni-
versal junction box with four tapped holes for 3/4” rigid conduit (three close-
up plugs included). Double wall remote has junction box with two tapped
holes for 3/4” rigid conduit (one close-up plug provided). DEEM1(2) fixture
is designed for direct mounting to the HC50N battery unit (HC50N unit not
included).
3. Electronics: 120/277 VAC dual voltage input with surge-protected, solid-
state circuitry. Charging system is complete with low voltage disconnect, AC
lockout, brownout protection, AC indicator lamp and test switch.
4. Battery: Choice of maintenance-free, sealed lead calcium battery with
5-year life and operating temperature range of 65°F (19°C) to 85°F (30°C), or
maintenance free, sealed nickel cadmium battery with 10-year life and oper-
ating temperature range of 20°F (-7°C) to 95°F (35°C).
5. Input Power Requirements: 120 VAC - 0.58 amps, 65 watts max; 277 VAC
- 0.27 amps, 68 watts max.
6. Warranty: Electronics: 3 years; Battery: 1 year full, 4 years pro-rata (lead
calcium); 5 years full, 5 years pro-rata (nickel cadmium)
Code Compliance
UL 924 listed.
Accessories