LG Electronics ESG-2008-V1 Air Conditioner User Manual


 
Flex Multi-
Split Indoor
Units
Outdoor
Units
Model
LMN090CE
LMAN090CNS
LMN120CE
LMAN120CNS
LMAN121CNM
LMN090HE
LMAN090HNS
LMN120HE
LMAN120HNS
LMAN121HNM
LMU180CE
LMU240CE
LMU360CE
LMU180HE
LMU240HE
LMU360HE
Voltage
Indoor
Outdoor
36V DC
36V DC
36V DC
36V DC
36V DC
36V DC
36V DC
36V DC
36V DC
36V DC
230/208
230/208
230/208
230/208
230/208
230/208
BTUs
9,000
9,000
12,000
12,000
12,000
9,000
9,000
12,000
12,000
12,000
18,000
24,000
36,000
18,000
24,000
36,000
Electrical Specifications
Wire Size
Minimum wiring requirements suggested by manufacturer
Minimum AWG 14-3
12-3***
Indoor/Outdoor Connecting Cable Minimum AWG 18-4
25'maximum
8'minimum
16.4'maximum
OILTRAP
INDOORUNIT
OUTDOORUNIT
FLEX MULTI-SPLIT • DUAL-ZONE & TRI-ZONE
ELECTRICAL & REFRIGERATION QUICK REFERENCE
Single-Zone Split Systems
Floor Standing
24,000 BTUs44,000 BTUs
24,000 BTUs
Single-Zone Split Systems
Ceiling Cassette
DUCT-FREE
FLOOR STANDING &
CEILING CASSETTE
AIR CONDITIONING
SYSTEMS
High-Capacity Split Systems
The Floor Standing and Ceiling Cassette models
are ideal for light commercial applications and
work well in large, open spaces. The Ceiling
Cassette is a useful alternative when floor space
is limited.
The outdoor unit for both models operate on
high-voltage (230/208) power and models one
or two compressors, depending on the size.
Duct-Free Split
Floor Standing Indoor Units
White Finish
Duct-Free Split
Ceiling Cassette Indoor Units
White Finish
Type
A/C
A/C
A/C
A/C
A/C
H/P
H/P
H/P
H/P
H/P
A/C
A/C
A/C
H/P
H/P
H/P
Rated
Amps
0.5
1.3
0.5
1.3
0.5
0.5
1.3
0.5
1.3
0.5
8.8
10.2
16.6
8.8
10.2
16.6
MCA*
15
20
30
15
20
30
MOP**
20
25
40
20
25
40
NOTE: Systems having the outdoor unit mounted above the indoor unit (e.g. basement installations) have the following
additional requirement: For systems with maximum elevation of 25 ft. (see chart above and Figure A), refrigerant lines
must be oil-trapped between 8 ft. and 16.4 ft. of elevation. For systems with elevation of greater than 25 ft. (see chart
above), refrigerant lines must be oil-trapped at least every 16.4 ft. of elevation.
Dual-Zone: Exterior unit has sufficient refrigerant for charging two indoor coils and a 25 ft. line set per indoor unit.
Tri-Zone: Exterior unit has sufficient refrigerant for charging three indoor coils and a 25 ft. line set per indoor unit.
34,000 BTUs
Figure A.
Example: 25 ft.
maximum
elevation.
29
30
FLOOR STANDING & CEILING CASSETTE
Flex Multi-
Split
Type
A/C
A/C
A/C
A/C
A/C
H/P
H/P
H/P
H/P
H/P
Model
LMN090CE
LMAN090CNS
LMN120CE
LMAN120CNS
LMAN121CNM
LMN090HE
LMAN090HNS
LMN120HE
LMAN120HNS
LMAN121HNM
Pipe size
Liquid
Suction
1/4" 3/8"
1/4"
3/8"
1/4" 3/8"
1/4" 3/8"
1/4" 3/8"
1/4" 3/8"
1/4" 3/8"
1/4" 3/8"
1/4" 3/8"
1/4" 3/8"
BTUs
9,000
9,000
12,000
12,000
12,000
9,000
9,000
12,000
12,000
12,000
Additional
Refrigerant
0.22 oz./ft.
0.22 oz./ft.
0.22 oz./ft.
0.22 oz./ft.
0.22 oz./ft.
0.22 oz./ft.
0.22 oz./ft.
0.22 oz./ft.
0.22 oz./ft.
0.22 oz./ft.
Max. Pipe
Length
50'
50'
50'
50'
50'
50'
50'
50'
50'
50'
Max.
Elevation
25'
25'
25'
25'
25'
25'
25'
25'
25'
25'
Refrigerant Line & Formula Specifications
All equipment are single phase.
NOTE: Please see local electrical codes for proper wire specifications.
*Minimum Circuit Ampacity **Maximum Overcurrent Protection ***For LMU360CE,
LMU360HE