LG Electronics ESG-2008-V1 Air Conditioner User Manual


 
Warranty: 2 years parts; 5 years compressor.
See page 20 for electrical specifications, refrigerant line requirements & formulas. See page 21 for installation materials.
19
HIGH WALL DUCT-FREE • MINI-SPLIT STANDARD SINGLE ZONE • INVERTER
25'maximum
8'minimum
16.4'maximum
OILTRAP
INDOORUNIT
OUTDOORUNIT
Each system is pre-charged with enough refrigerant to charge 25 ft. of line and the interior unit.
NOTE: Systems having the outdoor unit mounted above the indoor unit (e.g. basement
installations) have the following additional requirement: For systems
with elevation of 25 ft. (see chart above and figure A), refrigerant lines must be
oil trapped between 8 ft. and 16.4 ft. of elevation. For systems with elevation of greater than 25
ft. (see chart above), refrigerant lines must be oil trapped at least every 16.4 ft. of elevation.
Inverter
R-410A Refrigerant
Plasma air purifying system
Gold Fin™ Anti-Corrosion
Chaos Swing
Self-cleaning indoor coil
Auto changeover
Jet Cool
Cooling/Heating/Fan Mode
Auto sleep mode
Ultra-quiet operation
Dehumidifying mode
Auto restart
24-Hour on/off timer
Built-in low ambient standard,
down to 14ºF (cooling mode)
Manual power switch
Defrost control
Temperature display on
indoor unit
Evaporator frost control
Energy Saving
4 Fan speeds
Interior Unit Includes:
Wall unit
Installation plate & hardware
Remote control, batteries,
holder & holder hardware
Installation manual
Exterior Unit Includes:
Exterior unit
Exterior unit has sufficient
refrigerant for charging indoor
coil and a 25' line set (line set
not included)
System Model # LS305HV
Indoor Model # LSN305HV
Outdoor Model # LSU305HV
Performance
Capacity (BTUs) 27,000/27,000
29,000/29,000
SEER 16
Air Circulation (CFM H/M/L) 710/640/530
Fan Speeds 4/Auto/Chaos
Dehumidification (pts/hr) 7.2
Indoor dB(A)* 47/42/39
Outdoor dB(A)* 58
Electrical
Rated Voltage Outdoor 230/208-60-1
Rated Voltage Indoor 230/208-60-1
Indoor Dimensions 47 3/5 x
W x H x D (inches) 13 3/5 x
8 1/4
Weight (lbs.) 37.5
Outdoor Dimensions 34 1/4 x
W x H x D (inches) 31 1/4 x
12 3/5
Weight (lbs.) 147.7
Thermostat Range
Cooling / Heating (°F) 64-86 /60-86
*LG verified sound ratings.
MINI-SPLIT STANDARD SINGLE ZONE
ELECTRICAL & REFRIGERATION QUICK REFERENCE
Figure A: Example of 25 ft.
maximum elevation.
*Minimum Circuit Ampacity; **Maximum Overcurrent
Protection; ***For LS182HE, LS242CE/HE
Wire Size
Minimum wiring requirements suggested by manufacturer.
Minimum AWG 14-3
12-3***
Indoor/Outdoor Connecting Cable Minimum AWG 18-4
All equipment single phase.
NOTE: Please see local electrical codes for proper
wire specifications.
20
FEATURES:
30,000 BTUs
LS305HV (H/P Model)
27,000 BTUs Cooling
29,000 BTUs Heating
Electrical Specifications
Type
Model BTUs Voltage Rated MCA* MOP**
Indoor Outdoor
Amps
Mini-Split
A/C
LS092CE 9,000
36V DC
115 7.0 15 15
Standard
A/C
LS122CE 11,500 36V DC 115 10.5 15 20
Single-Zone
A/C
LS182CE 18,000 36V DC 230/208 8.6/9.5 15 20
A/C
LS242CE 22,500 36V DC 230/208 11.5/12.5 20 30
H/P
LS092HE 9,800 36V DC 115 10.5 15 20
H/P
LS122HE 11,500 36V DC 115 10.5 15 20
H/P
LS182HE 19,500 36V DC 230/208 11.5/12.5 20 30
H/P
LS242HE 22,500 36V DC 230/208 11.5/12.5 20 30
H/P
LS305HV
27,000/
29,000
230/208 230/208 13.6/14.0 20 30
Refrigerant Line & Formula Specifications
Type
Model BTUs Pipe Size Additional Max. Pipe Max.
Liquid
Suction Refrigerant Length Elevation
Mini-Split
A/C
LS092CE 9,000 1/4" 3/8" 0.22 oz./ft. 50' 25'
Standard
A/C
LS122CE 11,500 1/4" 1/2" 0.22 oz./ft. 50' 25'
Single-Zone
A/C
LS182CE 18,000 1/4" 1/2" 0.22 oz./ft. 100' 50'
A/C
LS242CE 22,500 1/4" 5/8" 0.22 oz./ft. 50' 50'
H/P
LS092HE 9,800 1/2" 115 0.22 oz./ft. 50' 25'
H/P
LS122HE 11,500 1/2" 115 0.22 oz./ft. 50' 25'
H/P
LS182HE 19,500 1/4" 5/8" 0.22 oz./ft. 100' 50'
H/P
LS242HE 22,500 1/4" 5/8" 0.22 oz./ft. 100' 50'
H/P
LS305HV
27,000/
29,000