Warranty: 2 years parts; 5 years compressor.
See page 20 for electrical specifications, refrigerant line requirements & formulas. See page 21 for installation materials.
19
HIGH WALL DUCT-FREE • MINI-SPLIT STANDARD SINGLE ZONE • INVERTER
25'maximum
8'minimum
16.4'maximum
OILTRAP
INDOORUNIT
OUTDOORUNIT
†
Each system is pre-charged with enough refrigerant to charge 25 ft. of line and the interior unit.
NOTE: Systems having the outdoor unit mounted above the indoor unit (e.g. basement
installations) have the following additional requirement: For systems
with elevation of 25 ft. (see chart above and figure A), refrigerant lines must be
oil trapped between 8 ft. and 16.4 ft. of elevation. For systems with elevation of greater than 25
ft. (see chart above), refrigerant lines must be oil trapped at least every 16.4 ft. of elevation.
• Inverter
• R-410A Refrigerant
• Plasma air purifying system
• Gold Fin™ Anti-Corrosion
• Chaos Swing
• Self-cleaning indoor coil
• Auto changeover
• Jet Cool
• Cooling/Heating/Fan Mode
• Auto sleep mode
• Ultra-quiet operation
• Dehumidifying mode
• Auto restart
• 24-Hour on/off timer
• Built-in low ambient standard,
down to 14ºF (cooling mode)
• Manual power switch
• Defrost control
• Temperature display on
indoor unit
• Evaporator frost control
• Energy Saving
• 4 Fan speeds
Interior Unit Includes:
• Wall unit
• Installation plate & hardware
• Remote control, batteries,
holder & holder hardware
• Installation manual
Exterior Unit Includes:
• Exterior unit
• Exterior unit has sufficient
refrigerant for charging indoor
coil and a 25' line set (line set
not included)
System Model # LS305HV
Indoor Model # LSN305HV
Outdoor Model # LSU305HV
Performance
Capacity (BTUs) 27,000/27,000
29,000/29,000
SEER 16
Air Circulation (CFM H/M/L) 710/640/530
Fan Speeds 4/Auto/Chaos
Dehumidification (pts/hr) 7.2
Indoor dB(A)* 47/42/39
Outdoor dB(A)* 58
Electrical
Rated Voltage Outdoor 230/208-60-1
Rated Voltage Indoor 230/208-60-1
Indoor Dimensions 47 3/5 x
W x H x D (inches) 13 3/5 x
8 1/4
Weight (lbs.) 37.5
Outdoor Dimensions 34 1/4 x
W x H x D (inches) 31 1/4 x
12 3/5
Weight (lbs.) 147.7
Thermostat Range
Cooling / Heating (°F) 64-86 /60-86
*LG verified sound ratings.
MINI-SPLIT STANDARD SINGLE ZONE
ELECTRICAL & REFRIGERATION • QUICK REFERENCE
Figure A: Example of 25 ft.
maximum elevation.
*Minimum Circuit Ampacity; **Maximum Overcurrent
Protection; ***For LS182HE, LS242CE/HE
Wire Size
Minimum wiring requirements suggested by manufacturer.
Minimum AWG 14-3
12-3***
Indoor/Outdoor Connecting Cable Minimum AWG 18-4
All equipment single phase.
NOTE: Please see local electrical codes for proper
wire specifications.
20
FEATURES:
30,000 BTUs
LS305HV (H/P Model)
27,000 BTUs Cooling
29,000 BTUs Heating
Electrical Specifications
Type
Model BTUs Voltage Rated MCA* MOP**
Indoor Outdoor
Amps
Mini-Split
A/C
LS092CE 9,000
36V DC
115 7.0 15 15
Standard
A/C
LS122CE 11,500 36V DC 115 10.5 15 20
Single-Zone
A/C
LS182CE 18,000 36V DC 230/208 8.6/9.5 15 20
A/C
LS242CE 22,500 36V DC 230/208 11.5/12.5 20 30
H/P
LS092HE 9,800 36V DC 115 10.5 15 20
H/P
LS122HE 11,500 36V DC 115 10.5 15 20
H/P
LS182HE 19,500 36V DC 230/208 11.5/12.5 20 30
H/P
LS242HE 22,500 36V DC 230/208 11.5/12.5 20 30
H/P
LS305HV
27,000/
29,000
230/208 230/208 13.6/14.0 20 30
Refrigerant Line & Formula Specifications
†
Type
Model BTUs Pipe Size Additional Max. Pipe Max.
Liquid
Suction Refrigerant Length Elevation
Mini-Split
A/C
LS092CE 9,000 1/4" 3/8" 0.22 oz./ft. 50' 25'
Standard
A/C
LS122CE 11,500 1/4" 1/2" 0.22 oz./ft. 50' 25'
Single-Zone
A/C
LS182CE 18,000 1/4" 1/2" 0.22 oz./ft. 100' 50'
A/C
LS242CE 22,500 1/4" 5/8" 0.22 oz./ft. 50' 50'
H/P
LS092HE 9,800 1/2" 115 0.22 oz./ft. 50' 25'
H/P
LS122HE 11,500 1/2" 115 0.22 oz./ft. 50' 25'
H/P
LS182HE 19,500 1/4" 5/8" 0.22 oz./ft. 100' 50'
H/P
LS242HE 22,500 1/4" 5/8" 0.22 oz./ft. 100' 50'
H/P
LS305HV
27,000/
29,000
1/4" 5/8" 0.22 oz./ft. 100' 50'