Accurate, Efficient, and Quiet Fan Coil Operation
• One or 3 hour Auto override - Fan speed
defaults to "Auto" mode after 1 hour if the
user manually changes it to a particular
fan speed.
• Temperature set range: 64-88 degrees F.
• Adjustable high and low temperature set
points
• Selectable Fahrenheit / Centigrade display
• Power switch turns system off/on
• Requires 7-wire 24V thermostat wire
• No batteries required
• Set points are permanently retained in
memory in case of power interruption
• Simple operation
• Mercury Free
• Wall plate included
For ceiling fan coils and vertical console units, op-
tional controls are factory installed, which include
the control board, transformer, and disconnect
switch. For MB/MB-HW and CW/CW-HW/CWE
series upflow or horizontal fan coils, the optional
control board and transformer can be factory
installed inside the unit wiring compartment. A
disconnect switch is not available with the MB/MB-
HW and CW/CW-HW/CWE models.
(Shown with wall plate)
• Compatible with 2 pipe and 4 pipe fan coils
Series HBC/PHBC/RHBC/CHBC,
MB/MB-HW, HYB/PHYB, and CW/CW-
HW/CWE
• Cycle fan or continuous fan operation
• T200-Manual Heat / Cool changeover
switch
• T201-Automatic Heat / Cool changeover
• Large LED digital display
• Allows less expensive 24V control
wiring from the fan coil to the thermostat,
rather than larger, more expensive line
voltage wiring.
• 3-speed fan operation, with speed indicator
lights
• Fan speed determination:
• If room temperature is 4 degrees
(F.) off thermostat set point, fan
will operate on High speed.
• If 3 degrees off set point, fan will
operate on Medium speed.
• If within 2 degrees of set point,
fan will operate on Low speed.
T200/T201 Thermostat Features
AUTOMATIC
FAN SPEED CONTROL
First Operations, LP. - P.O. BOX 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.firstco.com
The new Autospeed 24V™ thermostat (part #'s
T200 and T201) provides 24V AC single stage tem-
perature control of 2 pipe and 4 pipe fan coil applica-
tions. The T200/T201 thermostat offers maximum
comfort and efficiency by automatically selecting the
appropriate High, Medium, or Low fan speed, de-
pending on room temperature and thermostat tem-
perature setting. This automatic fan speed control
not only brings the room temperature to the desired
set point quickly, it maintains the room temperature
with the most efficient fan speed selection. Once the
desired room temperature is achieved the fan coil
operates on low speed for extremely quiet operation.
The fan coil control board
is a circuit board that pro-
vides control of a 3-speed line voltage (120, 208-240,
or 277V), (50 or 60 cycle) fan motor. The control
board allows the thermostat to control the fan motor
even though, by itself, the thermostat does not have
the current capability nor voltage rating capability to
control the fan motor. Contact the factory for various
control board part numbers.
The "Autospeed 24V
™
"
Control Package:
24V Digital 3-speed Wall Thermostat
and Fan Coil Control Board
For 2 pipe and 4 pipe fan coils
®
DISPLAY CODES
DISPLAY STEADY FLASHING
P1 Auto fan timer - 1 hour (default) Auto fan timer - 3 hour
P2 Continuous fan (default) Cycled fan
P3
o
F (default)
o
C
P4 Cycled fan standard Cycled fan overdrive
(default)
P5 Low temo limit 64
o
F (default) Low temp limit 67
o
F
P6 Hi temp limit 88
o
F (default) Hi temp limit 84
o
F