Honeywell Q682A Thermostat User Manual


 
1 69-0637—2
D. F. • Rev. 12-94 • ©Honeywell Inc. 1994 • • Form Number 69-0637—2
Y8196A (T8196A Thermostat/
Q682A Subbase) Heating/Cooling New
Construction Thermostat/Subbase
Package—Installation Instructions
Preparation
Check thermostat and subbase suitability for the heat-
ing, cooling, or heating/cooling system. Refer to Table 1.
Assemble tools required: flat bladed screwdriver, hand
or power drill with 3/16-in. drill bit, wire cutter/stripper or
sharp knife, bubble level or plumb bob and line.
Assure power is off to the heating, cooling, or heating/
cooling system at the main fuse panel. Most buildings have
a separate switch box or circuit breaker for disconnecting
power to the heating and cooling (if applicable) equipment.
This thermostat is compatible with virtually all heating,
cooling or heating/cooling systems. Refer to Table 1 for
additional thermostat compatibility information.
TABLE 1—THERMOSTAT AND SYSTEM COMPATIBILITY.
Type of Heating System
to be Controlled Conditions/Compatibility
Electric (Line Voltage)—typical baseboard and
radiant
The R8239D1015 Isolating Relay or R841 Silent Switching
Center must be installed in the thermostat control circuit.
a
Gas—Direct Spark Ignition (DSI), Intermittent
Pilot (IP), and Standing Pilot (SP)
Compatible.
Heat Pump Compatible. Assure correct subbase identity is selected for fan
control and changeover control (O terminal for cool and B
terminal for heat). Jumper Y to W for heat pump compressor
control.
Hot Water Zone Honeywell 2-wire valves are compatible.
Some non-Honeywell 2-wire valves require an R8239D1015
Isolating Relay in the thermostat control circuit.
a
Some 3-wire valves require an R8239A1052 Isolating Relay
in the thermostat control circuit.
a, b
Oil Compatible.
Vent Damper Honeywell damper motors are compatible.
Some non-Honeywell damper motors require an R8239D1015
Isolating Relay in the thermostat control circuit.
a
Check
control amperage requirement.
Warm Air Zone Most are compatible.
a
If thermostat is not compatible with the system being controlled, the system will not operate. No hazard exists. The thermostat
will not be damaged unless it is used to directly control a line voltage system. A Honeywell R841 or R8239D1015 Isolating
Relay must be added to the thermostat control circuit for proper system operation.
b
Consult manufacturer for installation requirements.
Recycling Notice
This control contains mercury in a sealed tube. Do not
place control in the trash at the end of its useful life.
If this control is replacing a control that contains mer-
cury in a sealed tube, do not place your old control in the
trash.
Contact your local waste management authority for
instructions regarding recycling and the proper disposal of
this control, or of an old control containing mercury in a
sealed tube.