Graco 332305B Heat Pump User Manual


 
Operation / Data Log
40 332305B
Example Event Log 2: Pump cycle of an injector valve
system with a pressure switch feedback.
Common System Events are listed below.
Error Log
The Error Log lists Set Time and Clear Time for the last
400 faults and warnings. The most recent event is listed
first.
The log file is stored as:
GRACO/G3_{DMS_id}/{download date - YYYYm-
mDD}/ERRORLOG.CSV
Example: GRACO/G3_00025/20100911/ERROR-
LOG.CSV.
Sample Error Log
Date Time Description
9/29/2010 13:28:12 Venting Completed
9/29/2010 13:23:12 Venting Detected
9/29/2010 13:23:11 Pump Run Off
9/29/2010 13:23:11 P1 Pressure Completed
9/29/2010 13:22:20 Pump Run On
Pump Run On The pump entered an on cycle and is
operating and dispensing material.
Pump Run Off The pump entered an off cycle and is
not dispensing.
Pump Run Can-
celled
A pump on cycle was cancelled by
pressing the cancel button on the front
panel and holding it for 3 seconds.
G3 Power On The pump powered on.
G3 Power Off The pump powered off.
Program Variable
Change
The setup mode was entered.
C1 Cycle Detected The system is set up to monitor a prox-
imity switch on a divider valve using the
sensor input (C1, C2, and/or C3) and
has detected one divider valve cycle.
C2 Cycle Detected
C3 Cycle Detected
C1 Cycle Com-
pleted
The system is set up to monitor a prox-
imity switch on a divider valve using the
sensor input (C1, C2, and/or C3) and
has achieved the number of counts
required by the system for that input,
completing a pump on cycle.
C2 Cycle Com-
pleted
C3 Cycle Com-
pleted
P1 Pressure Com-
pleted
The system is set up to monitor a pres-
sure switch for an injector system using
sensor input (P1, P2, and/or P3), the
system has achieved pressure and the
switch has activated, completing a
pump on cycle.
P2 Pressure Com-
pleted
P3 Pressure Com-
pleted
Machine Count
Completed
The system is set up to monitor a sen-
sor on the equipment being lubricated
using the machine count input and has
achieved the number of counts required
by the system for that input, completing
a pump off cycle and initiating a pump
on cycle.
Local Manual Run
Initiated
The manual run button was pressed,
initiating a pump on cycle.
Remote Manual
Run Initiated
The remote manual run button was
pressed initiating a pump on cycle.
Venting Detected In an injector system, the pump on cycle
has completed and the system is cur-
rently venting pressure through the vent
valve.
Prelube Initiated The pump has entered a prelube delay
after powering up.
Prelube Completed The pump has completed prelube delay
and will begin a pump on cycle.
Successful Pin
Code Entry
The pin code was successfully entered
and the user has entered setup mode.
G3 Error Log
DMS ID Number: 00025 (see page 38)
Software Part Number:16F821
Software Version:0205
12/31/2015 23:04:00
Date Time
Description
12/31/2015 23:03:54
Low Level Cleared
12/31/2015 23:03:42
Low Level Fault
12/31/2015 23:03:32
Low Level Warning
12/31/2015 23:03:22
P2 Not Detected Cleared
12/31/2015 23:03:22
C1 Not Detected Cleared
12/31/2015 23:03:19
P2 Not Detected
12/31/2015 23:03:19
C1 Not Detected
12/31/2015 23:02:20
Machine Count Not Detected
12/31/2015 23:02:11
Machine Count Not Detected