FMI (V)DVF36NS Indoor Fireplace User Manual


 
www.fmiproducts.com
125078-01B 15
Figure 16 - Installing Firestop
If area above is a living space, install
restop below framed hole.
If area above is an attic or insulated area,
install restop above framed hole.
Note: If vent pipe passes through any occupied ar-
eas above rst oor, including storage spaces and
closets, you must enclose pipe. You may frame
and sheetrock enclosure with standard construc-
tion material. Make sure and meet the minimum
allowable clearances to combustibles. Do not ll
any required air spaces with insulation.
Vertical Termination Congurations
Figure 17 shows the congurations for vertical
termination.
VENTING INSTALLATION
Continued
Figure 17 - Vertical Venting Conguration
HIGH ALTITUDE INSTALLATION
Your FMI PRODUCTS, LLC direct vent
replace has been tested and approved for
elevations from 0-2000 feet.
Fireplaces for high altitude (-HA Models) are
for installations above 4,000 feet only. These
replaces are equipped with parts specic for
higher altitudes.
When installing a non-high altitude replace at
an elevation above 2000 feet, you may need
to decrease the input rating by changing the
existing burner orice to a smaller size. Reduce
input 4% for each 1000 feet above sea level.
Check with your local gas company for proper
orice size identication.
When installing this replace at an elevation
above 4500 feet, check with local authorities.
PARTS LIST FOR VENTING KITS
AND COMpONENTS
FMI (5/8") Pipe & Vent Kits
Number Description
P58-6 6" Section Double Wall Pipe,
Galvanized
P58-12 12" Section Double Wall Pipe,
Galvanized
P58-24 24" Section Double Wall Pipe,
Galvanized
P58-36 36" Section Double Wall Pipe,
Galvanized
P58-48 48" Section Double Wall Pipe,
Galvanized
PA58-712 Adjustable 7"-12" Section Double
Wall Pipe, Galvanized
E58-45 45° Elbow, Galvanized
E58-90 90° Elbow, Galvanized
HTS-58 Horizontal Square Termination,
Galvanized
HHT-58 High Wind Round Termination,
Galvanized
VT-58 Vertical Round Termination,
Galvanized
SC-58 Storm Collar, Galvanized
WF-58 Wall Firestop, Galvanized
RF-58-6 Roof Flashing - 0 to 6/12 Pitch,
Galvanized
RF-58-12 Roof Flashing - 6/12 to 12/12 Pitch,
Galvanized
VR-58 Vertical Restrictor, Galvanized
S-58 Vinyl Siding Standoff, Galvanized
WS-58 Wall Strap
CS-58 Cathedral Ceiling Support
FP-58 Firestop Plate
SF-58 Stucco Flashing - For use with
HTS-58
RF-58 Flat Roof Flashing
Vertical
Venting
V = 40' max.