Empire Comfort Systems VFSR-24-3 Electric Heater User Manual


 
Page 718954-0-0705
PROVISIONS FOR ADEQUATE COMBUSTION & VENTILATION AIR
Minimum Dimensions For Solid Fuel Burning Fireplaces UL127
Factory Built Fireplaces (Figure 2)
Model A B C D
VFSV-16 18" 11 1/2" 24" 18"
VFSR-16 18" 11 1/2" 24" 18"
VFSV-18 17" 14" 28" 17"
VFSR-18 17" 14" 28" 17"
VFSM-18 21" 14" 32" 17"
VFSV-24 23" 14" 30" 18"
VFSR-24 23" 14" 30" 18"
VFSM-24 27" 14" 34" 18"
VFSV-30 26" 14" 34" 20"
VFSR-30 26" 14" 34" 20"
VFSM-30 30" 14" 38" 20"
The dimensions shown and defined in the fireplace manufacturer’s
instructions are minimum clearances to maintain in installing this
heater. Left and right clearances are determined when facing the
front of the heater.
CLEARANCES
Figure 2
This heater shall not be installed in a confined space unless provisions
are provided for adequate combustion and ventilation air.
The National Fuel Gas Code defines a confined space as a space whose
volume is less than 50 cubic feet per 1,000 Btu per hour (4.8m
3
per kw)
of the aggregate input rating of all appliances installed in that space and
an unconfined space as a space whose volume is not less than 50 cubic
feet per 1,000 Btu per hour (4.8 m
3
per kw) of the aggregate input rating
of all appliances installed in that space. Rooms communicating directly
with the space in which the appliances are installed, through openings
not furnished with doors, are considered a part of the unconfined space.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough fresh
air for combustion and ventilation. However, in buildings of unusually
tight construction, you must provide additional fresh air.
Unusually tight construction is defined as construction where:
a. Walls and ceilings exposed to the outside atmosphere have a
continuous water vapor retarder with a rating of one perm or less
with openings gasketed or sealed, and
b. Weatherstripping has been added on openable windows and doors,
and
c. Caulking or sealants are applied to areas such as joints around
window and door frames, between sole plates and floors, between
wall-ceiling joints, between wall panels, at penetrations for plumb-
ing, electrical, and gas lines, and at other openings.
If your home meets all of the three criteria above, you must provide
additional fresh air.
Warning: If the area in which the heater may be operated is smaller than
that defined as an unconfined space or if the building is of unusually tight
construction, provide adequate combustion and ventilation air by one
of the methods described in the National Fuel Gas Code, ANSI Z223.1,
Section 5.3. or applicable local codes.
Example of Large Room with 1/2 Wall divider.
Figure 1
The following formula can be used to determine the maximum heater rating
per the definition of unconfined space:
Btu/Hr =
(L
1
+ L
2
)FT x (W)FT x (H)FT
x 1000
50
If the area in which the heater may be operated is smaller than that defined
as an unconfined space, provide adequate combustion and ventilation air
by one of the methods described in the National Fuel Gas Code, ANSI
Z223.1, Section 5.3.
Adhere to all codes, or in their absence, the latest edition of THE
NATIONAL FUEL GAS CODE ANSI Z223.1 or NFPA54 which can be
obtained from:
American National Standards Institute National Fire Protection Association, Inc.
11 West 42nd St. Batterymarch Park
New York, NY 10018 Quincy, MA 02269
Glass Doors
Make sure that glass doors are open during all operations of
the logset. The opening of the glass door frame should be
the dimension used for the minimum front opening of the
firebox.
Follow these instructions to ensure safe
installation.
Failure to follow
instructions exactly
can create a fire
hazard.