EMI WCP Air Cleaner User Manual


 
Web: http://www.enviromaster.comEnviromaster International LLC
PRODUCT DESCRIPTION
The WCP is a contemporary design, chilled water air handler
that combines attractive appearance in any decor, with the
highly efcient conditioning of small to mid size commercial
or residential spaces. Equipped with unit mounted infrared
compatible controls, optional hand held remote also
available.
Units provide up to a nominal 30,000 Btuh of cooling. Electric
heat options are available for up to 5KW of supplemental
heat. It can be paired with a matching capacity chilled water
supply. This all American made unit offers ease of installation,
operation and service.
Factory Installed Controls/Components:
• Relays and connections for chilled water supply
• Unit mounted digital controls as standard:
– Large ¾” LCD display
– Anti-short cycle protection
– Fan purge (fan remains on for 60 seconds after
heat/cool call dropped for improved efciency)
• Auto/high/low fan operation
• Low Volt transformer
NOTE: Auto fan operation automatically selects
fan speed according to heating or cooling demand.
Constant fan operation is manually selected high or
low speed.
Materials of Construction:
• Cabinet (available in designer white with grey discharge
vanes) fabricated of cold roll steel with structural stiff-
eners
• Air inlet panel made from high impact polystyrene with
perforated steel grille
• Discharge grille constructed of high temperature Noryl
• Condensate drain pan made from galvanized steel
(G90U) with anti-corrosion coating
OPTIONAL EQUIPMENT
• Hand held infra-red remote controller (a separate hand
held remote controller used to command the on-board
controls).
NOTE: Unit mounted controls are fully functional
without the remote controller.
• Field installed condensate pump
• 24V remote thermostat with controls & relays
• Chilled water control valve (N/C 24V ac, 20VA max. or
8 VA max. on units with condensate pumps)
• Electric heat with automatic reset high temperature
cutout and redundant high temperature fuse link.
INSTALLER SUPPLIED ITEMS
• Power wiring & low voltage wiring
• Mounting screws and fasteners
• Chilled water & condensate piping
WCP
HigH Wall air Handler
SpecificationS and performance
P/N# 240003248 Rev. A [06/08]
AIR HANDLER STANDARD FEATURES
2 PiPe CHilled Water Fan Coil
Nominal Capacities: 9000, 12000,
15000, 18000, 24000, 30000 Btuh
WCP CAPACITIES
Model
Nominal
Capacaties
Total
Capacity
Sensible
Capacity
Fluid
Temp.
Fluid
Flow
PD
Ft. H
2
0
09/12
9,000
7,375 6,732 45 1 0.8
10,801 8,272 45 2 3.8
13,270 9,279 45 3 8.0
12,000
8,387 7,189 40 1 0.8
12,481 8,950 40 2 3.9
15,643 10,304 40 3 8.1
15 /18
15,000
15,624 13,477 45 2 4.4
19,761 15,367 45 3 9.1
18,000
17,724 14,379 40 2 4.5
23,073 16,763 40 3 9.3
24/30
24,000
20,563 17,564 45 3 2.3
29,031 21,178 45 6 8.3
32,320 22,539 45 9 17.7
30,000
23,600 18,887 40 3 2.4
34,400 23,423 40 6 8.4
38,790 25,351 40 9 17.9