Ei Electronics Ei154TL Smoke Alarm User Manual


 
Shannon Free Zone, Shannon, Co. Clare, Ireland.
Ph.+353 61 471277 Fx.+353 61 471053
Email. eielectronics@eiltd.ie
Web: www.eielectronics.com
E & OE As our policy is one of continuous product development, we reserve the right to alter product details without prior notice. Ei154TL DataSht RevB
Model Ei154TL Heat
Tamper proof rechargeable lithium battery back up
Fixed temperature fast response thermistor type
sensor, range 54°C to 62°C
Test button
Advanced suppression and calibration technology
Interconnectable to other Ei mains powered alarms
Low power cell warning
Kitemarked to BS5446-2:2003
5 year guarantee
Product Description
The Ei154TL is a Heat Alarm that runs on 230V AC
mains power, and has built in tamper proof rechargeable
lithium cells that act as a battery back up in the event of
mains failure. These rechargeable lithium cells are
designed to have a ten year life and outlast the life of the
heat alarm itself, whilst providing up to six months of
heat alarm operation without mains power.
The Ei154TL has advanced features such as the ability
to interconnect up to twelve alarms to allow all alarms to
sound if just one of the interconnected alarms should be
triggered.
The Ei154TL has built in circuitry to aid suppression of
voltage transients and RF interference to further reduce
the chances of false alarms under such conditions.
The Ei154TL heat alarm gives a fire warning when the
temperature at the unit reaches 58
0
C. Heat alarms are
ideal for use in kitchens and garages, where the use of
optical or ionisation alarms would lead to unwanted
nuisance alarms
On escape routes this alarm must be interconnected
with smoke alarms.
Operation
The green indicator will illuminate to show mains
power is present
The red indicator will flash every 40 seconds to
show that the detector has performed an automatic
self test
The red indicator will flash rapidly to show an alarm
condition for the smoke detector
The “Test” button will perform a unit self test and
sound the horn
When interconnected to other Ei mains powered
alarms, an alarm on one detector will trigger all other
interconnected alarms within one second (only the
triggered alarm will flash a red indicator)
The heat detector will emit a beep every 40 seconds
to indicate that the battery back up is depleted and
needs recharging
MAINS POWERED 230V~
Rechargeable Battery Back-Up