Error Display!
Error
Status
Initializing
No Input Sensor
Connected
Input Signal
Error
Exceeding
Upper Limit
Exceeding
Lower Limit
Exceeding Setup Range
PV
Flashing
SV
N/A N/A N/A
Note
Initializing.
Displaying
software version
and the type of
input sensor.
The input voltage is
too big, connecting
to empty terminal, or
incorrect sensor.
Cannot get
temperature
value, ADC
input error.
The displayed
value exceeds
10,999.
The displayed
value is
smaller than
-1,999.
The input exceeds TP-H
(Max. temp), TP-L (Min.
temp), or the range of
the input sensor
selected.
How to Mount!
1. Insert DTD into the panel cutout.
2. Insert the mounting bracket into the mounting groove at the top and bottom of DTD.
3. Push the mounting bracket forward until the bracket stops at the panel wall.
4. Tighten the screw.
How to Install Mounting Bracket!
Panel Cutout!
DTD4848
65.0 min.
6
0
.
0
m
i
n
.
45
+0.6
0
4
5
+
0
.
6
0
DTD7272
DTD4896
6