Delkin Devices EI - 25-1 Indoor Fireplace User Manual


 
EURO 25 -1 26
SERVICING
Before servicing, read the terms and conditions of the Archgard warranty at the back of the
manual. Contact the Archgard authorized dealer from which you have purchased the appliance
and provide him with details of the problem and the installation information which the installer
has filled out at the back of this manual.
WARNING: Servicing of this appliance must be conducted by a qualified service technician.
Improper servicing, adjustment or alteration of this appliance may cause
property damage, personal injury or loss of life. All servicing should be
conducted with the appliance cold.
The primary air shutter is located underneath the burner.
Loosen the air shutter set screw with a Philips ‘+’ or a #3 Robertson ‘’ screwdriver.
Rotate air shutter by hand. The primary air opening size can be easily seen.
Tighten the air shutter set screw after adjustment.
CAUTION: Adjust the primary air shutter only when the appliance is cool to the touch.
SERVICING UNDER WARRANTY
Remove the control cover.
The pressure test taps are located on the front of the valve. The supply pressure is marked
IN’ and the manifold pressure is marked ‘OUT’. There is also an arrow marking the
direction of gas flow.
Loosen the set screw inside the tap with a ” wide flat screw driver.
Connect a ¼” rubber tube to the tap and a pressure gauge.
Be sure to tighten the set screw inside the tap after you are finish taking
pressure readings and check for gas leaks.
CHECKING SUPPLY AND MANIFOLD GAS PRESSURE
The pilot flame should fully envelop the thermocouple and thermopile with a strong blue cone flame. If
a lazy flame is observed this could cause the unit to shut down.
ADJUSTING PRIMARY AIR
PILOT ADJUSTMENT