Cooper Lighting BETA 50 Indoor Furnishings User Manual


 
Catalog #
Project
Comments
Prepared by
Type
Date
SPECIFICATION FEATURES
09/22/2008 12:05:52 PM
Consult your representative for additional options and finishes.
Specifications and Dimensions subject to change without notice.
ADC041684
DOOR FRAME
MOUNTING DIMENSIONS
LAMP CONFIGURATIONS
DESCRIPTION
The Fail-Safe MAF Series is designed for use in horizontal or non-laminar air
flow clean rooms. The enclosed and gasketed housing and one-piece, out-
side flanged door protect against infiltration of airborne bacteria. The die
formed edges on the door frame and the hole-free design of the housing
prevent air exchange between the fixture and plenum, allowing relamping
without contamination of the clean areas. These luminaires are U.L. listed
and C.S.A. certified for wet locations and manufactured in accordance with
U.S.D.A., F.D.A., N.S.F. and Federal Standard 209E guidelines. Rated for
high pressure hose down at 200 PSI.
Application
Applications include surgical
suites, clean rooms, technical and
biomedical labs, food processing/
testing centers and pharmaceutical
labs.
A ... Lens
(To be specified.) One-piece, clear
extruded lens with internal prism
pattern. Choice of prismatic acrylic,
prismatic polycarbonate, Radialens
(TM) or prismatic tempered glass
on environmental side. See Lens
Options.
B ... Fasteners
Flush mounted, stainless steel
machine screws secure through
captive cage nuts in housing and
are evenly spaced to compress
gasketing on all sides.
C ... Housing
Die-formed, 20 ga. CRS with tightly
butted and seam welded, sealed
end caps. Contains no holes that
would allow air passage. Standard
white high reflectance polyester
powder coat finish. Gloss: 85%;
Reflectance: 93%; Hardness: 2H;
Salt Spray: 500 Hours.
D ... Lamps
(By Others)
E ... Lens Retention
Unique, Particulock(TM) lens
retention system utilizes
continuous, 18 ga. media
clampdowns to sandwich
gasketing and integrate lens and
door frame for even environmental
seal.
F ... Hinge
Two braided, stainless steel cables
on one side of door provide
hinging.
G ... Door
(To be specified.) One-piece, 18
ga., fully gasketed, outside flanged
door with die-formed edges
eliminates seams which could
entrap microscopic contaminants.
H ... Ballast
Standard Class P, CBM/ETL ballast.
I ... Gasket
White, closed cell, Flexiseal(TM)
gasketing surrounds perimeter of
lens to seal lens to door frame and
around perimeter of door to seal
door to housing. Another layer on
the flange seals fixture to ceiling
system after installation.
J ... Access
A gasketed access plate on top of
the housing with two flattened,
7/8" diameter knockouts allows
connection of vapor tight conduit
fitting.
Labels
U.L. listed, C.S.A. certified,
standard wet label.
MAF
17W - 40W
Fluorescent
1' X 4'
FLUORESCENT FLANGE
Symmetric/Asymmetric Lens
One-Piece Door
Flange Type-One-Piece Door
C
B
DH J
A
F
I
G
E
4 3/8"
[111mm]
4"
[102mm]
10 3/4"
[273mm]
12 1/4"
[311mm]
14"
[356mm]
1 1/2"
[38mm]
3 11/16"
[94mm]
11 1/16" [281mm]
Ceiling Cut-Out
13 1/4"
[336mm]
(2) 7/8" [22mm] KO
Gasketed Access Plate
(4) 3/16" [5mm] Dia.
Yoke Mounting Hole
36"
[914mm]
48 5/16" [1227mm]
Ceiling Cut-Out
3"
[76mm]
1 3/4"
[44mm]
1 3/4"
[44mm]
2"
[51mm]
ENERGY DATA
Input Watts:
STD Ballasts & STD Lamps
(1) 20W T12 Fluorescent: 32W
(2) 20W T12 Fluorescents: 53W
(3) 20W T12 Fluorescents: 85W
(1) 40W Biaxial Fluorescent: 45W
(2) 40W Biaxial Fluorescents: 82W
ES Ballasts & STD Lamps
(1) 17W T8 Fluorescent: 23W
(2) 17W T8 Fluorescents: 45W
(3) 17W T8 Fluorescents: 68W
(1) 32W T8 Fluorescent: 37W
(2) 32W T8 Fluorescents: 71W
(3) 32W T8 Fluorescents: 108W
(1) 40W T12 Fluorescent: 50W
(2) 40W T12 Fluorescents: 86W
(3) 40W T12 Fluorescents: 136W
ES Ballasts & ES Lamps
(1) 40W T12 Fluorescent: 44W
(2) 40W T12 Fluorescents: 7
6W
(3) 40W T12 Fluorescents: 120W
Electronic Ballast Data:
Consult Factory
FAIL-SAFE
®