Chromalox CHPES-6A Boiler User Manual


 
3 Phase Voltages*
Output
Quantity/Rating
Elec at
of Contactors
No./kW
Rating Cap. Vol. 212˚F Heating
Model (BHP) (kW) (Gals.) (Lbs./Hr.)
208 240 480†
Elements
Type CHPES — 20-250 PSIG
CHPES-6A 0.6 6 6 18 30 30 30 1-6
CHPES-9A 0.9 9 6 27 30 30 30 1-9
CHPES-12A 1.22 12 6 36.2 40 30 30 1-12
CHPES-18A 1.73 17 6 51.2 50 50 30 1-17
CHPES-24A 2.45 24 14.3 72.3 2-40 2-30 2-30 2-12
1-40 1-40 1-12
CHPES-30A 2.95 29 14.3 87.4
1-50 1-30
40
1-17
CHPES-36A 3.47 34 14.3 102.5 2-50 2-50 50 2-17
1-40 1-30 1-40 1-12
CHPES-48A 4.69 46 14.3 138.7
2-50 2-50 1-30 2-17
2-50 2-30 2-12
CHPES-60A 5.91 58 14.3 174.8
2-40 2-50
2-40
2-17
CHPES-72A 6.93 68 14.3 205 4-50 4-50 2-50 4-17
CHPES-100A 10.40 102 27.8 307 6-50 6-50 3-50 6-17
CHPES-135A 13.9 136 30.5 410 8-50 4-50 8-17
1-30
CHPES-160A 16.1 157.5 30.5 475 7-60
3-60
7-22.5
CHPES-180A 18.4 180 30.5 543 8-60 4-60 8-22.5
Chromalox
®
DIVISION
4
SECTION
CHPES
SALES
REFERENCE
DATE
SERVICE REFERENCE
Installation, Operation
and
RENEWAL PARTS IDENTIFICATION
PQ436-1
MAY, 1999
(Supersedes PQ436)
161-562802-002
© 2010 Chromalox, Inc.
Type CHPES-6A through CHPES-180A
High Pressure Electric Steam Boiler
Standard Trim is 250 PSI — 0-225 PSI Operating Pressure Range
Boiler Serial Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Circuit Voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Model. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Control Circuit Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
National Board No. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Amps . . . . . . . . . . . . . . . Phase . . . . . . . . . . . Cy . . . . . . . . . .
Important — This data file contains the National Board Registration Certificate for your boiler. It must be kept near the boiler at all times.
* Single phase available up to and including 24 kW capacity.
† All boilers must have separate 120V Control Circuit or Transformer.
Boilers under 40 Amps max are not fused.