Carrier TJF004 Air Conditioner User Manual


 
37
START-UP
Unit Preparation
Make sure that unit has been in-
stalled in accordance with these installation instructions and
applicable codes.
Return-Air Filters
Make sure correct filters are in-
stalled in filter tracks. See Table 1. Do not operate unit without
return-air filters.
Compressor Mounting
Compressors are internally
spring mounted. Do not loosen or remove compressor hold-
down bolts.
Internal Wiring
Check all electrical connections in
unit control boxes. Tighten as required. Ensure electrical wires
do not come in contact with refrigerant tubing or sharp edges.
Refrigerant Service Ports
To service refrigerant
service ports, remove refrigerant service port access panel. See
Fig. 43. Each unit system has 4 Schrader-type service gage
ports: one on the suction line, one on the liquid line, and two on
the compressor discharge line. Be sure that caps on the ports
are tight. When a controls upgrade package is used, one
Schrader-type valve is located under both the high-pressure
switch and the low-pressure switch.
High Flow Valves
Located on the compressor hot gas
and suction tubes are High Flow Valves. Large black plastic
caps distinguish these valves with o-rings located inside the
caps. These valves can not be accessed for service in the field.
Ensure the plastic caps are in place and tight or the possibility
of refrigerant leakage could occur.
Compressor Rotation
On 3-phase units with scroll
compressors, it is important to be certain compressor is rotating
in the proper direction. To determine whether or not compres-
sor is rotating in the proper direction:
1. Connect service gages to suction and discharge pressure
fittings.
2. Energize the unit.
3. The suction pressure should drop and the discharge pres-
sure should rise, as is normal on any start-up.
If the suction pressure does not drop and the discharge pres-
sure does not rise to normal levels:
1. Note that the evaporator fan is probably also rotating in
the wrong direction.
2. Turn off power to the unit and install lockout tag.
3. Reverse any two of the unit power leads.
4. Reapply power to unit and recheck pressures.
The suction and discharge pressure levels should now move
to their normal start-up levels.
NOTE: When the compressor is rotating in the wrong direc-
tion, the unit makes an elevated level of noise and does not
provide cooling.
Cooling
Set space thermostat of OFF position. To start
unit, turn on main power supply. Set system selector switch at
COOL position and fan switch at AUTO. position. Adjust ther-
mostat to a setting below room temperature. Compressor starts
on closure of contactor.
Check unit charge. Refer to Service, Refrigerant Charge
section, page 41. Allow unit to operate a minimum of 10 min-
utes before checking charge.
Reset thermostat at a position above room temperature.
Compressor will shut off. Evaporator fan will shut off after
30-second delay.
TO SHUT OFF UNIT — Set system selector switch at OFF
position. Resetting thermostat at a position above room tem-
perature shuts unit off temporarily until space temperature ex-
ceeds thermostat setting.
Main Burners
Main burners are factory set and should
require no adjustment.
TO CHECK ignition of main burners and heating controls,
move thermostat set point above room temperature and verify
that the burners light and evaporator fan is energized. After en-
suring that the unit continues to heat the building, lower the
thermostat setting below room temperature and verify that the
burners and evaporator fan turn off. (Fan will turn off only if
fan selector switch is in the AUTO. position and after a
45-second delay has elapsed.)
Refer to Table 30 for the correct orifice to use at high
altitudes.
Table 30 Altitude Compensation*
*As the height above sea level increases, there is less oxygen per
cubic foot of air. Therefore, heat input rate should be reduced at
higher altitudes.
Orifices available through your Carrier distributor.
ELEVATION
(ft)
74,000 AND 115,000
BTUH NOMINAL
INPUT
150,000 BTUH
NOMINAL INPUT
Natural
Gas
Orifice
Size
Liquid
Propane
Orifice
Size
Natural
Gas
Orifice
Size
Liquid
Propane
Orifice
Size
0-2,000
33 43 30 38
2,000
34 43 30 39
3,000
35 44 31 40
4,000
36 44 32 41
5,000
36 44 33 42
6,000
37 45 34 43
7,000
37 45 35 43
8,000
38 46 36 44
9,000
39 47 37 44
10,000
41 48 38 45
11,000
43 48 39 45
12,000
44 49 40 46
13,000
44 49 41 47
14,000
45 50 42 47
Fig. 43 Service Panel Location