26
Table 16 — Fan Performance 48TJ006 — Vertical Discharge Units, High-Static Motor
LEGEND
*Motor drive range is 1300 to 1685 rpm. All other rpms require a field-
supplied drive.
NOTES:
1.
Boldface
indicates field-supplied drive is required.
2. indicates field-supplied motor and drive are required.
3. Values include losses for filters, unit casing, and wet coils. See
Table 7 for accessory/FIOP static pressure information.
4. Maximum continuous bhp is 2.9 and the maximum continuous
watts are 2562. Extensive motor and electrical testing on these
units ensures that the full range of the motor can be utilized with
confidence. Using your fan motors up to the wattage ratings shown
will not result in nuisance tripping or premature motor failure. Unit
warranty will not be affected. See Table 6 — Motor Data for addi-
tional information.
5. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
6. Interpolation is permissible. Do not extrapolate.
48TJ006 (5 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
Airflow
(Cfm)
External Static Pressure (in. wg)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1500 808 0.42 429 914 0.56 572 1001 0.69 705 1084 0.85 869 1168 1.01 1032
1600 846 0.49 501 950 0.64 645 1034 0.78 797 1111 0.94 961 1194 1.11 1134
1700 884 0.57 592 983 0.72 736 1068 0.88 899 1145 1.03 1053 1218 1.21 1237
1800 942 0.66 674 1018 0.82 838 1105 0.98 1001 1179 1.13 1155 1246 1.32 1349
1900 965 0.78 777 1057 0.92 940 1143 1.10 1124 1212 1.26 1288 1280 1.43 1481
2000 1008 0.87 889 1096 1.04 1063 1177 1.22 1247 1247 1.40 1431
1300 1.57 1604
2100 1051 0.99 1012 1136 1.17 1196 1210 1.35 1380 1284 1.54 1574
1347 1.72 1758
2200 1095 1.12 1145 1173 1.30 1328 1245 1.49 1523
1322 1.70 1737 1380 1.89 1931
2300 1140 1.28 1288 1210 1.47 1502 1284 1.65 1686
1356 1.80 1901 1418 2.07 2115
2400 1185 1.41 1441 1249 1.61 1645
1323 1.80 1860 1389 2.03 2074 1456 2.26 2310
2500 1231 1.57 1604 1289 1.78 1819
1363 2.00 2044 1424 2.22 2269 1500 2.45 2504
48TJ006 (5 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)
Airflow
(Cfm)
External Static Pressure (in. wg)
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1500 1199 1.19 1216 1126 1.46 1492 1250 1.69 1757
1301 1.91 1944 1349 2.12 2164
1600 1263 1.28 1308 1275 1.49 1523 1299 1.78 1800
1352 2.01 2047 1401 2.23 2280
1700 1295 1.39 1420
1351 1.58 1615 1352 1.80 1850 1407 2.03 2070 1459 2.26 2305
1800
1319 1.52 1553 1389 1.71 1747 1453 1.91 1952 1494 2.15 2197 1548 2.40 2446
1900
1343 1.64 1676 1415 1.80 1891 1478 2.05 1095 1538 2.31 2358 1594 2.57 2625
2000
1374 1.77 1809 1438 1.99 2034 1505 2.21 2258 1566 2.49 2542 1624 2.77 2830
2100
1409 1.91 1952 1465 2.14 2167 1533 2.45 2501 1596 2.77 2821
1654 3.08 3141
2200
1442 2.08 2126 1498 2.30 2350 1568 2.64 2688
1632 2.97 3031 1691 3.31 3375
2300
1475 2.26 2310 1554 2.64 2698
1627 3.03 3091 1693 3.42 3486 1755 3.81 3881
2400
1565 2.47 2524 1649 2.89 2948
1726 3.31 3379 ——————
2500
1596 2.95 3010 1682 3.45 3522 1760 3.96 4036 ——————
Bhp —
Brake Horsepower Input to Fan
FIOP —
Factory-Installed Option
Watts —
Input Watts to Motor