Carrier RVS Heat Pump User Manual


 
26
Table 7 — 50RDS, RHS, RVS Electrical Data
LEGEND
PRE-START-UP
System Checkout —
When the installation is complete,
follow the system checkout procedure outlined below before
starting up the system. Be sure:
1. Voltage is within the utilization range specifications of the
unit compressor and fan motor and voltage is balanced
for 3 phase units.
2. Fuses, breakers and wire are correct size.
3. Low voltage wiring is complete.
4. Piping and system flushing is complete.
5. Air is purged from closed loop system.
6. System is balanced as required. Monitor if necessary.
7. Isolation valves are open.
8. Water control valves or loop pumps are wired.
9. Condensate line is open and correctly pitched.
10. Transformer switched to lower voltage tap if necessary.
11. Blower rotates freely — shipping support is removed.
12. Blower speed is on correct setting.
13. Air filter is clean and in position.
14. Service/access panels are in place.
15. Return-air temperature is between 40 to 80 F heating and
50 to 110 F cooling.
16. Air coil is clean.
17. Control field selected settings are correct.
50RDS,
RHS,
RVS
UNIT
VOLTS-
PHASE
60 Hz
VOLTAGE
MIN/MAX
COMPRESSOR
FAN
MOTOR
FLA
TOTAL
UNIT
FLA
MIN
CIRCUIT
AMP
MAX
FUSE/HACR
UNITS WITH HWR
RLA LRA
REHEAT
PUMP
FLA
TOTAL
UNIT
FLA
MIN
CIRCUIT
AMP
MAX
FUSE /
HACR
015
208/230-1 197/254 4.9 26.0 1.00 5.9 7.2 15 0.8 6.7 7.9 15
265-1 239/292 4.4 28.0 0.86 5.2 6.3 15 0.7 8.0 7.1 15
018
208/230-1 197/254 7.1 38.0 1.00 8.1 9.8 15 0.8 8.9 10.7 15
265-1 239/292 5.5 32.0 0.86 6.4 7.8 15 0.7 7.1 8.5 15
024
208/230-1 197/254 10.3 56.0 1.10 11.4 13.9 20 0.8 12.8 15.5 25
265-1 239/292 8.7 47.0 0.90 9.6 11.7 20 0.7 10.6 12.9 20
208/230-3 197/254 7.1 45.0 1.10 8.2 9.9 15 0.8 9.0 10.8 20
460-3 414/506 3.5 22.4 0.57 4.1 5.0 15 0.7 4.8 5.7 15
030
208/230-1 197/254 12.2 67.0 1.30 13.5 16.5 25 0.8 14.3 17.4 25
265-1 239/292 10.9 56.0 1.58 12.5 15.2 25 0.7 13.2 15.9 25
208/230-3 197/254 7.7 55.0 1.30 9.0 10.9 15 0.8 9.8 11.7 15
460-3 414/506 3.8 27.0 0.85 4.7 5.7 15 0.7 5.4 6.4 15
030
HIGH
STATIC
208/230-1 197/254 12.2 67.0 1.30 13.5 16.5 25 0.8 14.8 17.9 30
265-1 239/292 10.9 56.0 1.58 12.5 15.2 25 0.7 13.6 16.3 25
208/230-3 197/254 7.7 55.0 1.30 9.0 10.9 15 0.8 10.3 12.2 15
460-3 414/506 3.8 27.0 0.85 4.7 5.7 15 0.7 5.8 6.8 15
036
208/230-1 197/254 13.5 73.0 1.80 15.3 18.6 30 0.8 16.1 19.5 30
265-1 239/292 12.8 71.0 2.00 14.8 18.0 30 0.7 15.5 18.7 30
208/230-3 197/254 9.6 63.0 1.80 11.4 13.8 20 0.8 12.2 14.6 20
460-3 414/506 4.5 31.0 1.24 5.7 6.8 15 0.7 6.5 7.6 15
036
HIGH
STATIC
208/230-1 197/254 13.5 73.0 1.80 15.3 18.6 30 0.8 17.3 20.7 30
265-1 239/292 12.8 71.0 2.00 14.8 18.0 30 0.7 16.2 19.4 30
208/230-3 197/254 9.6 63.0 1.80 11.4 13.8 20 0.8 13.4 15.8 25
460-3 414/506 4.5 31.0 1.24 5.7 6.8 15 0.7 6.9 8.0 15
042
208/230-1 197/254 16.5 95.0 1.90 18.4 22.6 35 0.8 19.2 23.3 35
208/230-3 197/254 10.3 77.0 1.90 12.2 14.7 25 0.8 13.0 15.6 25
460-3 414/506 5.1 39.0 1.00 6.1 7.4 15 0.7 6.8 8.1 15
575-3 518/633 4.2 31.0 0.80 5.0 6.1 15 N/A N/A N/A N/A
048
208/230-1 197/254 18.3 109.0 3.00 21.3 25.9 40 1.07 22.4 26.9 45
208/230-3 197/254 12.4 88.0 3.00 15.4 18.5 30 1.07 16.5 19.6 30
460-3 414/506 6.4 44.0 1.70 8.1 9.7 15 1.07 9.2 10.8 15
575-3 518/633 4.8 34.0 1.50 6.3 7.5 15 N/A N/A N/A N/A
060
208/230-1 197/254 25.0 169.0 3.40 28.4 34.6 50 1.07 29.5 35.7 60
208/230-3 197/254 17.3 123.0 3.40 20.7 25.0 40 1.07 21.8 26.1 40
460-3 414/506 6.7 49.5 1.80 8.5 10.2 15 1.07 9.6 11.2 15
575-3 518/633 5.8 40.0 1.60 7.4 8.8 15 N/A N/A N/A N/A
070
208/230-1 197/254 28.8 169.0 4.30 33.1 40.4 60 1.07 34.8 42.0 70
208/230-3 197/254 17.3 137.0 4.30 21.6 25.9 40 1.07 23.3 27.6 40
460-3 414/506 9.0 62.0 2.50 11.5 13.7 20 1.07 12.6 14.8 20
575-3 518/633 6.6 49.0 2.20 8.8 10.5 15 N/A N/A N/A N/A
FLA Full Load Amps LRA Locked Rotor Amps
HACR Heating, Air Conditioning and Refrigeration RLA Rated Load Amps
HWR Hot Water Reheat