Carrier RVS Heat Pump User Manual


 
24
Table 5 — 50RHC,RVC Electrical Data
LEGEND *Size 006 available in 50RHC unit only.
†Size 041 available in 50RVC unit only.
NOTES:
1. HACR circuit breaker in U.S.A. only.
2. All fuses Class RK-5.
50RHC,RVC
UNITS
VOLTS-PHASE
60 Hz
VOLTAGE
MIN/MAX
COMPRESSOR FAN
MOTOR
FLA
TOTAL
UNIT
FLA
MIN
CIRCUIT
AMP
MAX
FUSE/HACR
RLA LRA
006*
208/230-1 197/254 2.9 17.7 0.40 3.3 4.1 15
265-1 239/292 2.5 15.0 0.35 2.8 3.5 15
009
208/230-1 197/254 3.9 22.2 0.80 4.7 5.7 15
265-1 239/292 3.3 18.8 0.70 4.0 4.8 15
012
208/230-1 197/254 5.3 27.9 0.80 6.1 7.5 15
265-1 239/292 4.2 22.2 0.70 4.9 6.0 15
018
208/230-1 197/254 8.6 49.0 1.00 9.6 11.7 20
265-1 239/292 8.1 44.0 0.86 8.9 11.0 15
024
208/230-1 197/254 9.8 56.0 1.50 11.3 13.8 20
265-1 239/292 9.1 55.0 1.30 10.4 12.7 20
208/230-3 197/254 6.7 51.0 1.50 8.2 9.9 15
460-3 414/506 3.5 25.0 0.76 4.2 5.1 15
030
208/230-1 197/254 11.2 61.0 3.00 14.2 16.9 25
265-1 239/292 10.0 58.0 2.70 12.7 15.2 25
208/230-3 197/254 6.9 55.0 3.00 9.9 11.7 15
460-3 414/506 3.6 28.0 1.70 5.3 6.2 15
036
208/230-1 197/254 15.4 82.0 1.80 17.2 21.1 35
265-1 239/292 14.4 83.0 2.00 16.4 20.0 30
208/230-3 197/254 9.6 70.0 1.80 11.4 13.8 20
460-3 414/506 4.9 33.0 1.24 6.1 7.4 15
041†
208/230-1 197/254 16.2 96.0 3.00 19.2 23.2 35
208/230-3 197/254 10.3 75.0 3.00 13.3 15.8 25
460-3 414/506 4.3 40.0 1.70 6.0 7.1 15
575-3 518/633 4.3 34.0 1.40 5.7 6.8 15
042
208/230-1 197/254 17.1 105.0 3.00 20.1 24.3 40
208/230-3 197/254 10.7 85.0 3.00 13.7 16.4 25
460-3 414/506 5.3 42.0 1.70 7.0 8.3 15
575-3 518/633 3.7 31.0 1.50 5.2 6.1 15
048
208/230-1 197/254 18.3 102.0 3.40 21.7 26.3 40
208/230-3 197/254 12.6 91.0 3.40 16.0 19.2 30
460-3 414/506 5.7 42.0 1.80 7.5 8.9 15
575-3 518/633 4.7 39.0 1.40 6.1 7.2 15
060
208/230-1 197/254 25.6 170.0 4.30 29.9 36.4 60
208/230-3 197/254 14.7 124.0 4.30 19.0 22.7 35
460-3 414/506 7.4 59.6 2.50 9.9 11.8 15
575-3 518/633 5.9 49.4 1.90 7.8 9.3 15
FLA Full Load Amps
HACR Heating, Air Conditioning and Refrigeration
LRA Locked Rotor Amps
RLA Rated Load Amps