Carrier RVR Heat Pump User Manual


 
28
Table 9 — 50RHC,RVC Blower Performance
*Size 006 is available in 50RHC unit only.
†Size 041 is available in 50RVC unit only.
NOTES:
1. Gray areas denote ESP (external static pressure) where operation is not
recommended.
2. Units factory shipped on medium speed. Other speeds require field
selection.
3. All airflow is rated at lowest voltage if unit is dual voltage rated, i.e., 208 v
for 208-230 v units.
4. All units ARI/ISO/ASHRAE 13256-1 rated on high fan speed.
5. Only two-speed fan (H & M) available on 575-v units.
6. For wet coil performance first calculate the face velocity of the air
coil (Face Velocity [fpm] = Airflow [cfm]/Face Area [sq ft]). Then for veloci-
ties of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by
0.08 in. wg, 400 fpm by 0.12 in. wg, and 500 fpm by 0.16 in. wg.
7. Airflow in cfm with net dry coil and clean air filter.
Table 10 — 50RVC Blower Performance with Hot Water Reheat (HWR) Option
50RHC,RVC
UNITS
RATED
CFM
MIN
CFM
FAN
SPEED
AIRFLOW (Cfm)
External Static Pressure (in. wg)
0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.60 0.70 0.80 0.90 1.0 1.10 1.20 1.30
006* 220 150
HI
310 300 290 280 270 250 230 210 180
MED
260 250 240 230 210 200 190 150
LO 210 200 190 180 160 150
009 325 225
HI
410 400 380 360 350 330 320 300 280
MED 390 370 360 340 320 310 290 280 260
LO
340 330 322 310 300 280 260 250 220
012 400 300
HI
470 460 450 440 430 420 400 390 380 320
MED
420 410 400 390 380 370 360 350 340
LO
360 360 350 340 320 320 310 300 290
018 600 450
HI 760 740 720 710 700 680 650 600 550 460
MED 700 690 680 670 660 650 630 620 600 560 520 430
LO 620 610 600 590 580 570 560 540 520 490 460
018
High Static
600 450
HI
790 780 770 760 750 730 710 690 650 530 430
MED 750 740 720 710 700 690 670 670 660 650 630 600 490 390
LO 670 660 640 630 620 610 600 590 580 580 570 530 420
024 800 600
HI
1000 970 930 870 770 690
MED 1010 1000 990 980 960 940 920 900 880 860 830 770 700 600
LO 820 810 800 790 780 770 760 750 730 720 700 650 600
024
High Static
800 600
HI
1030 950 840 700
MED
1040 1010 970 890 750 620
LO 1030 1010 980 960 930 900 870 790 710
030 1000 750
HI
1160 1130 1100 1070 1030 950 840
MED 1250 1230 1200 1180 1150 1120 1090 1070 1040 1010 970 890 750
LO 1120 1100 1070 1050 1030 1010 980 960 930 900 870 790 710
030
High Static
1000 750
HI
1160 1040 920 800 750
MED
1130 1080 1030 930 820 750
LO 1050 1040 1030 1010 990 980 960 940 910 880 840 750
036 1200 900
HI 1520 1500 1480 1460 1430 1400 1370 1350 1320 1270 1210 1110 960 840
MED 1150 1150 1140 1140 1130 1130 1120 1110 1100 1070 1040 940
LO 1010 1010 1000 1000 990 990 980 980 970 950 930
036
High Static
1200 900
HI 1530 1500 1470 1400 1290 1170 960
MED 1360 1350 1340 1330 1320 1310 1300 1280 1260 1250 1230 1150 1070 910
LO 1030 1020 1010 1010 1000 1000 990 980 960 950 930
041† 1325 950
HI 1380 1370 1350 1330 1300 1260 1220 1170 1120 1080 1040 890
MED 1230 1220 1200 1190 1180 1150 1120 1080 1030 990 950
LO 1040 1030 1010 1000 990 970 950
042 1350 1050
HI 1640 1610 1580 1550 1520 1490 1450 1410 1370 1330 1290 1190 1100
MED 1490 1470 1440 1420 1390 1370 1340 1310 1270 1230 1190 1120 1010
LO 1140 1140 1130 1130 1120 1110 1100 1080 1060 1010
042
High Static
1350 1050
HI
1550 1540 1520 1500 1470 1460 1450 1380 1240 1080
MED 1390 1380 1370 1360 1350 1340 1320 1310 1300 1280 1250 1180 1080
LO
048 1600 1200
HI
1980 1950 1910 1860 1800 1740 1680 1490 1280 1280
MED 1940 1920 1900 1880 1860 1820 1770 1740 1710 1660 1600 1410 1000
LO 1770 1750 1730 1710 1690 1670 1650 1610 1570 1510 1450 1330
048
High Static
1600 1200
HI
2060 2040 2010 1960 1880 1790 1660 1510
MED 2050 2050 2040 2020 1990 1970 1940 1920 1890 1860 1830 1780 1710 1620 1490 1320
LO 1850 1850 1840 1830 1810 1800 1780 1760 1730 1700 1670 1600 1510 1380 1220
060 2000 1500
HI 2240 2240 2230 2220 2200 2160 2120 2090 2060 2040 2010 1960 1880 1790 1660 1510
MED 2050 2050 2040 2020 1990 1970 1940 1920 1890 1860 1830 1780 1710 1620 1490
LO 1850 1850 1840 1830 1810 1800 1780 1760 1730 1700 1670 1600 1510
060
High Static
2000 1500
HI 2400 2400 2390 2380 2370 2360 2340 2320 2300 2270 2240 2200 2130 2060 1980 1890 1790 1660 1500
MED 2160 2160 2150 2150 2140 2110 2080 2060 2040 2030 2020 1980 1930 1880 1490 1750 1660 1530
LO 1930 1930 1920 1920 1910 1900 1890 1890 1880 1870 1850 1830 1800 1750 1700 1620 1530
REHEAT EXTERNAL STATIC PRESSURE (ESP) LOSS
COIL FACE VELOCITY
(fpm)
018, 024, 030
(in. wg)
036, 042
(in. wg)
048, 060
(in. wg)
200 0.060 0.049 0.038
250 0.070 0.055 0.040
300 0.090 0.068 0.045
350 0.124 0.091 0.059
400 0.164 0.129 0.094
450 0.252 0.221 0.189
500 0.380 0.350 0.320
NOTE: For 50RVC units with HWR, calculate coil face velocity of the entering air. Find the
external static pressure loss for the reheat application. This loss includes the wet coil loss.