Carrier NP034-074 Air Conditioner User Manual


 
Table 7 Electrical Data, 074 Units
208/230-3-60 (V-Ph-Hz)
VOLTAGE
RANGE
COMPR
NO. 1
COMPR
NO. 2
OFM IFM
BASE UNIT
ONLY
EXHAUST
FAN
ELECTRIC
HEAT*
BASE UNIT WITH
EXHAUST FAN
AND/OR
ELECTRIC HEAT*
RLA LRA RLA LRA
Total
FLA
Hp FLA MCA MOCP
Total
Hp
Total
FLA
kW FLA MCA MOCP
187-254 107.7 506.0 142.3 690.0 27.8
15.0
46.2/
42.0
358.8/
854.6
500/
450
10.0 33.4/30.4 392.2/385.0 500/500
15.0 48.4/44.0 407.2/398.6 500/500
20.0 61.6/56.0 420.4/410.6 500/500
29/ 36 78.9/ 91.0 358.8/354.6 500/450
59/ 72 157.7/182.0 358.8/354.6 500/450
88/108† 236.6/273.0 358.8/393.8 500/450
10.0 33.4/30.4 29/ 36 78.9/ 91.0 392.2/385.0 500/500
10.0 33.4/30.4 59/ 72 157.7/182.0 392.2/385.0 500/500
10.0 33.4/30.4 88/108† 236.6/273.0 392.2/393.8 500/500
15.0 48.4/44.0 29/ 36 78.9/ 91.0 407.2/398.6 500/500
15.0 48.4/44.0 59/ 72 157.7/182.0 407.2/398.6 500/500
15.0 48.4/44.0 88/108† 236.6/273.0 407.2/398.6 500/500
20.0 61.6/56.0 29/ 36 78.9/ 91.0 420.4/410.6 500/500
20.0 61.6/56.0 59/ 72 157.7/182.0 420.4/410.6 500/500
20.0 61.6/56.0 88/108† 236.6/273.0 420.4/410.6 500/500
20.0
59.4/
64.0
372.0/
366.6
500/
500
10.0 33.4/30.4 405.4/397.0 500/500
15.0 48.4/44.0 420.4/410.6 500/500
20.0 61.6/56.0 433.6/422.6 500/500
29/ 36 78.9/ 91.0 372.0/366.6 500/500
59/ 72 157.7/182.0 372.0/366.6 500/500
88/108† 236.6/273.0 372.0/408.8 500/500
10.0 33.4/30.4 29/ 36 78.9/ 91.0 405.4/397.0 500/500
10.0 33.4/30.4 59/ 72 157.7/182.0 405.4/397.0 500/500
10.0 33.4/30.4 88/108† 236.6/273.0 405.4/408.8 500/500
15.0 48.4/44.0 29/ 36 78.9/ 91.0 420.4/410.6 500/500
15.0 48.4/44.0 59/ 72 157.7/182.0 420.4/410.6 500/500
15.0 48.4/44.0 88/108† 236.6/273.0 420.4/410.6 500/500
20.0 61.6/56.0 29/ 36 78.9/ 91.0 433.6/422.6 500/500
20.0 61.6/56.0 59/ 72 157.7/182.0 433.6/422.6 500/500
20.0 61.6/56.0 88/108† 236.6/273.0 433.6/422.6 500/500
25.0
74.8/
68.0
387.4/
380.6
500/
500
10.0 33.4/30.4 420.8/411.0 500/500
15.0 48.4/44.0 435.8/424.6 500/500
20.0 61.6/56.0 449.0/436.6 500/500
29/ 36 78.9/ 91.0 387.4/380.6 500/500
59/ 72 157.7/182.0 387.4/380.6 500/500
88/108† 236.6/273.0 389.3/426.3 500/500
10.0 33.4/30.4 29/ 36 78.9/ 91.0 420.8/411.0 500/500
10.0 33.4/30.4 59/ 72 157.7/182.0 420.8/411.0 500/500
10.0 33.4/30.4 88/108† 236.6/273.0 420.8/426.3 500/500
15.0 48.4/44.0 29/ 36 78.9/ 91.0 435.8/424.6 500/500
15.0 48.4/44.0 59/ 72 157.7/182.0 435.8/424.6 500/500
15.0 48.4/44.0 88/108† 236.6/273.0 435.8/426.3 500/500
20.0 61.6/56.0 29/ 36 78.9/ 91.0 449.0/436.6 500/500
20.0 61.6/56.0 59/ 72 157.7/182.0 449.0/436.6 500/500
20.0 61.6/56.0 88/108† 236.6/273.0 449.0/436.6 500/500
30.0
88.0/
80.0
400.6/
392.6
500/
500
10.0 33.4/30.4 434.0/423.0 500/500
15.0 48.4/44.0 449.0/436.6 500/500
20.0 61.6/56.0 462.2/448.6 600/500
29/ 36 78.9/ 91.0 400.6/392.6 500/500
59/ 72 157.7/182.0 400.6/392.6 500/500
88/108† 236.6/273.0 405.7/441.3 500/500
10.0 33.4/30.4 29/ 36 78.9/ 91.0 434.0/423.0 500/500
10.0 33.4/30.4 59/ 72 157.7/182.0 434.0/423.0 500/500
10.0 33.4/30.4 88/108† 236.6/273.0 434.0/441.3 500/500
15.0 48.4/44.0 29/ 36 78.9/ 91.0 449.0/436.6 500/500
15.0 48.4/44.0 59/ 72 157.7/182.0 449.0/436.6 500/500
15.0 48.4/44.0 88/108† 236.6/273.0 449.0/441.3 500/500
20.0 61.6/56.0 29/ 36 78.9/ 91.0 462.2/448.6 600/500
20.0 61.6/56.0 59/ 72 157.7/182.0 462.2/448.6 600/500
20.0 61.6/66.0 88/108† 236.6/273.0 462.2/448.6 600/500
LEGEND
CV Constant Volume
ETL ETL Testing Laboratory
FLA Full Load Amps
Hp Nominal Horsepower
IFM Indoor (Evaporator) Fan Motor
LRA Locked Rotor Amps
MCA Minimum Circuit Amps (for wire sizing)
MOCP Maximum Overcurrent Protection
OFM Outdoor (Condenser) Fan Motor
RLA Rated Load Amps
*Electric heat available on 50 Series vertical discharge units.
†108 kW available on CV applications only.
NOTES:
1. Electric resistance heaters are rated at 208/240 v, 480 v, or 575 v. To
determine heater capacity (kW) at unit operating voltage, multiply 240 v,
480 v, or 575 v capacity by appropriate multiplier below.
MULTIPLICATION FACTORS
HEATER kW
RATING
VOLTAGE
DISTRIBUTION
V-3-60
MULTIPLICATION
FACTOR
240
200
208
230
240
0.694
0.751
0.918
1.000
480
440
460
480
0.840
0.918
1.000
575
550
575
600
0.915
1.000
1.089
Electric heaters are tested and ETL approved at maximum
total external static pressure of 1.9 in. wg.
2. Boldface indicates 48 and 50 Series units. All other data is for 50 Series
units only.
31