Carrier 38APS025-050 Air Conditioner User Manual


 
71
APPENDIX A — DISPLAY TABLES (cont)
Configuration Mode and Sub-Mode Directory
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
DISP
DISPLAY CONFIGURATION
TEST ON/OFF Test Display LEDs
METR ON/OFF Metric Display Off = English On = Metric
LANG X Language Selection
Default: 0
0 = English
1 = Espanol
2 = Francais
3 = Portuguese
PAS.E ENBL/DSBL Password Enable
PASS XXXX Service Password
UNIT
UNIT CONFIGURATION
SIZE Unit Size
NCKT X Number of Refrigerant Circuits
SZ.A1 XX Compressor A1 Size
SZ.A2 XX Compressor A2 Size
SZ.A3 XX Compressor A3 Size
SZ.B1 XX Compressor B1 Size
SZ.B2 XX Compressor B2 Size
SZ.B3 XX Compressor B3 Size
FAN.S XX Fan Sequence Number
A1.TY YES/NO Compressor A1 Digital
MAX.T XX Maximum A1 Unload Time
CCN
CCN NETWORK CONFIGS
CCNA XXX CCN Address
Default: 1
Range: 0 to 239
CCNB XXX CCN Bus Number
Default: 1
Range: 0 to 239
BAUD X CCN Baud Rate
Default: 3
1 = 2400
2 = 4800
3 = 9600
4 =19,200
5 =38,400
OPT1
UNIT OPTIONS 1 HARDWARE
MLV.S YES/NO Minimum Load Valve Select
CSB.E ENBL/DSBL CSB Boards Enable
SPT.S ENBL/DSBL Space Temp Sensor
SPOS ENBL/DSBL Space Temp Offset Enable
SPOR XX Space Temp Offset Range 1 to 10
RAT.T X RAT Thermistor Type
Default: 0
0 = 5 K
1 = 10 K
2 = None
SAT.T X SAT Thermistor Type
Default: 0
0 = 5 K
1 = 10 K
2 = None
EMM YES/NO EMM Module installed
OPT2
UNIT OPTIONS 2 CONTROLS
C.TYP X Machine Control Type
Default: 4
1 = VAV
2 = Invalid
3 = TSTAT MULTI
4 = TSTAT 2 STG
5 = SPT MULTI
6 = Invalid
7 = PCT CAP
8 = DUAL TSTAT
9 = VAV SETPOINT
CTRL X Control Method
Default: 0
0 = Enable/Off/Remote Switch
1 = Occupancy
2 = CCN Control
LOAD X Loading Sequence Select
Default: 1
1 = Equal
2 = Staged
LLCS X Lead/Lag Circuit Select
Default: 1
1 = Automatic
2 = Circuit A Leads
3 = Circuit B Leads
DELY XX Minutes Off Time
Default: 0
Range: 0 to 15 Minutes