Carrier 38APS025-050 Air Conditioner User Manual


 
69
APPENDIX A — DISPLAY TABLES (cont)
Temperature Mode and Sub-Mode Directory
Pressures Mode and Sub-Mode Directory
Set Points Mode and Sub-Mode Directory
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
UNIT
ENTERING AND LEAVING UNIT TEMPERATURES
RAT xxx.x °F Return Air Temperature
SAT xxx.x °F Supply Air Temperature
OAT xxx.x °F Outside Air Temperature
SPT xxx.x °F Space Temperature
SCT.D xxx.x ΔF Circuit SCT Difference
CIR.A
TEMPERATURES CIRCUIT A
SCT.A xxx.x °F Saturated Condensing Tmp
SST.A xxx.x °F Saturated Suction Temp
RGT.A xxx.x °F Compr Return Gas Temp
D.GAS xxx.x °F Discharge Gas Temp
SH.A xxx.x ΔF Suction Superheat Temp
CIR.B
TEMPERATURES CIRCUIT B
SCT.B xxx.x °F Saturated Condensing Tmp
SST.B xxx.x °F Saturated Suction Temp
RGT.B xxx.x °F Compr Return Gas Temp
SH.B xxx.x ΔF Suction Superheat Temp
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
PRC.A
PRESSURES CIRCUIT A
DP.A XXX.XPSIG Discharge Pressure
SP.A XXX.XPSIG Suction Pressure
PRC.B
PRESSURES CIRCUIT B
DP.B XXX.XPSIG Discharge Pressure
SP.B XXX.XPSIG Suction Pressure
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION RANGE COMMENT
COOL
COOLING SET POINTS
CSP.1 xxx.x °F Cooling Set Point 1 40 to 80 Default: 55 F
CSP.2 xxx.x °F Cooling Set Point 2 40 to 80 Default: 50 F
SPS.P xxx.x °F Space T Cool Set Point 65 to 80 Default: 78 F
SPT.O xx.x ΔF Space Temperature Offset
STP.O xxx.x °F Space T SP Plus Offset
P.CAP XXX Percent CAP Requested
LCON xx.x ΔF Lo Cool On Set Point –1 to 2 Default: 1
HCON xx.x ΔF HI Cool On Set Point 0.5 to 20 Default: 3
LCOF xx.x ΔF Lo Cool Off Set Point 0.5 to 2 Default: 0.5
HEAD
HEAD PRESSURE SET POINTS
H.SP xxx.x °F Head Set Point ON 85 to 120 Default: 110 F
HSPF xxx.x °F Head Set Point OFF 45 to 90 Default: 72 F
F.ON xxx.x °F Fan On Set Point
F.OFF xxx.x °F Fan Off Set Point
F.DLT XX.X Fan Stage Delta 0 to 50
F.TME XXX Fan Delta Active Time 0 to 300