APPENDIX A — DISPLAY TABLES (cont)
Run Status Mode and Sub-Mode Directory (cont)
Service Test Mode and Sub-Mode Directory
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
STRT
COMPRESSOR STARTS
ST.A1 XXXX Compressor A1 Starts
ST.A2 XXXX Compressor A2 Starts
ST.A3 XXXX Compressor A3 Starts
ST.B1 XXXX Compressor B1 Starts
ST.B2 XXXX Compressor B2 Starts
ST.B3 XXXX Compressor B3 Starts
PM
PREVENTIVE MAINTENANCE
COIL COIL MAINTENANCE
SI.CL xxxx HRS Coil Cleaning Srvc Int
C.L.DN xxxx HRS Coil Service Countdown
C.L.MN YES/NO Coil Cleaning Maint.Done User Entry
CL.DT COIL MAINTENANCE DATES
C.L.M0 MM/DD/YY HH:MM
C.L.M1 MM/DD/YY HH:MM
C.L.M2 MM/DD/YY HH:MM
C.L.M3 MM/DD/YY HH:MM
C.L.M4 MM/DD/YY HH:MM
VERS
SOFTWARE VERSION NUMBERS
MBB CESR131279-XXXXX
AUX CESR131333-XXXXX
CXB CESR131173-XXXXX
EMM CESR131174-XXXXX
MARQ CESR131171-XXXXX
NAVI CESR130227-XXXXX
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
TEST Service Test Mode
To enable Service Test mode, move
Enable/Off/Remote contact switch to
OFF. Change TEST to ON.
Move switch to ENABLE
OUTS
OUTPUTS
FAN1 ON/OFF Fan 1 Relay
FAN2 ON/OFF Fan 2 Relay
FAN3 ON/OFF Fan 3 Relay
FAN4 ON/OFF Fan 4 Relay
FAN5 ON/OFF Fan 5 Relay
V.HPA xx Var Head Press % Cir A
V.HPB xx Var Head Press % Cir B
DIG.P xx Comp A1 Load Percent
LSV.A ON/OFF Liquid Line Solenoid A
LSV.B ON/OFF Liquid Line Solenoid B
RMT.A ON/OFF Remote Alarm Relay
CMPA
CIRCUIT A COMPRESSOR TEST
CC.A1 ON/OFF Compressor A1 Relay
UL.TM xx Comp A1 Unload Time
CC.A2 ON/OFF Compressor A2 Relay
CC.A3 ON/OFF Compressor A3 Relay
MLV ON/OFF Minimum Load Valve Relay
CMPB
CIRCUIT B COMPRESSOR TEST
CC.B1 ON/OFF Compressor B1 Relay
CC.B2 ON/OFF Compressor B2 Relay
CC.B3 ON/OFF Compressor B3 Relay