Carrier 19XR Fan User Manual


 
RATED DRY WEIGHT AND REFRIGERANT CAPACITY
ENGLISH (lb)
TANK
SIZE
TANK OD
(in.)
DRY
WEIGHT*
(lb)
MAXIMUM REFRIGERANT CAPACITY (lb)
ANSI/ASHRAE 15 UL 1963
0428 24.00 2380 1860 1716
0452 27.25 3460 3563 3286
SI (kg)
TANK
SIZE
TANK OD
(mm)
DRY
WEIGHT*
(kg)
MAXIMUM REFRIGERANT CAPACITY (kg)
ANSI/ASHRAE 15 UL 1963
0428 610 1080 844 778
0452 592 1569 1616 1491
LEGEND
ASHRAE American Society of Heating, Refrigeration,
and Air Conditioning Engineers
OD Outside Diameter
UL Underwriters’ Laboratories
*The above dry weight includes the pumpout condensing unit weight of 210 lbs (95 kg).
Fig. 19 Optional Pumpout Unit and Storage Tank (cont)
26