Bryan Boilers BE Series Water Heater User Manual


 
BE Series
Indirect Water Heaters
Electric
Form 2221 Rev 02/13/08 Repl 02/01/04 Page 1 of 1
Please delete these paragraphs from
the standard BE Series Boiler Sample
Specification:
The boiler shall be a Bryan Model ________
electric boiler, with a capacity of ________ KW
at ________ volts. (________ HP)
The boiler shall be constructed and assembled
as a completely packaged unit factory tested and
UL labeled. The boiler shall be ready for field
connections to the water supply, return
connection, electrical power supply, relief valve
discharge, and building management controls.
The water boiler shall be manufactured in strict
accordance with the ASME Heating Boiler Code,
Section IV, and shall bear the ASME stamp “H”
for a maximum working pressure of 150 PSIG
and 250
o
F temperature.
And substitute these paragraphs:
The water heater shall be a Bryan Model
________ Indirect Electric Water Heater, with a
capacity of ________ KW at_______ volts and
water heating capacity of ________ gallons per
hour, with a temperature rise from ________
o
F
to ________
o
F.
The water heater shall be constructed and
assembled as a completely packaged unit
factory tested and UL labeled. The boiler shall
be ready for field connections to the water
supply, return connection, electrical power
supply, relief valve discharge, and building
management controls.
The water heater shall be manufactured in strict
accordance with the ASME Heating Boiler Code,
Section IV, and shall bear the ASME “H” stamp
for maximum working pressure of 125 PSIG and
250
o
F.
The water heater shall be furnished complete
with one or more indirect heat exchangers with a
maximum water discharge temperature of 150
o
F.
The heat exchanger(s) shall be installed in the
upper drum of the boiler, will be capable of
absorbing 100% of the total boiler output as
specified and rated operation temperatures.
Heat exchanger(s) to be constructed of heavy
copper seamless finned tubing, attached to
boiler shell by means of a gasket and stud type
connection and shall be easily removable and
replaceable.
WATER HEATER TRIM & CONTROLS
The water heater shall be furnished with
the following fittings and trim:
1. Automatic boiler fill valve
2. Expansion tank
3. ASME safety relief valve for heat exchanger
4. Boiler stop valve