HOT WATER TEMPERATURE FLUCTUATES
1. Unbalanced pressure in waterlines
The added restriction caused by the Aquastar in the hot
water system can result in uneven pressures between the
cold and the hot. In such cases when mixing cold water at
the tap, the lower hot water pressure may be overpowered
by a much higher cold water pressure, which may cause
the Aquastar burners to shut down. Make sure faucet
aerators or shower heads are free of minerals. Do not
add any flow restrictor to the shower head.
2. Cold water is mixing with the hot water between
the AquaStar and the outlet
See #4 under NO SPARK AT THE PILOT.
3. Inlet water pressure is erratic due to inadequate
supply water pressure or saturated pressure tank
on well system
Check the inlet water pressure. On a private well, raise
minimum pressure setting to 30 psi. Confirm that the
pressure tank is not water logged.
4. Gas pressure is too low
See page 2 for correct specifications.