Armstrong World Industries 123 Air Conditioner User Manual


 
Service Reference Manual INSTALLATION
6-9
SRM-HW/HWC 8/99
Removal of Unit from Common Venting
System
When an existing furnace is removed from a common venting system
serving other appliances, the venting system is likely to be too large to
properly vent the remaining attached appliances. The following test
should be conducted with each appliance while the other appliances
connected to the common venting system are not in operation.
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal
pitch and determine there is no blockage or restriction, leakage,
corrosion or other deficiencies which could cause an unsafe condi-
tion.
3. Insofar as is practical, close all building doors and windows between
the space in which the appliances remaining connected to the
common venting system are located and other spaces in the building.
Turn on clothes dryers and any appliance not connected to the
common venting system. Turn on exhaust fans, such as range hoods
and bathroom exhausts, so they will operate at maximum speed. Do
not operate a summer exhaust fan. Close fireplace dampers.
4. Following the lighting instructions, place the unit being inspected in
operation. Adjust the thermostat so the appliance will operate
continuously.
5. Test for spillage at the draft control relief opening after five minutes of
main burner operation. Use the flame of a match or candle.
6. Follow the preceding steps for each appliance connected to the
common venting system.
7. After it has been determined that each appliance remaining con-
nected to the common venting system properly vents when tested as
outlined above, return doors, windows, exhaust fans, fireplace
dampers and any other fuel burning appliance to their previous
condition of use.
8. If improper venting is observed during any of the above tests, the
common venting system must be corrected. See National Fuel
Gas Code, ANSI Z223.1 (latest edition) or CAN/CGA B149.1 & .2
Canadian Installation Codes to correct improper operation of
common venting system.
Gas Connections
The gas line to the unit should be adequately sized to prevent undue
pressure drop and should never be smaller than the manual valve used.
Consult the local utility or National Fuel Gas Code for complete details on
special requirements in sizing gas piping.
The units supplied for operation with natural gas contain a gas regulator
which must be operated with inlet gas pressures specified on the rating
plate. If gas line pressure exceeds this figure, an additional high pressure
regulator must be installed to reduce this pressure.