Aprilaire 61000652C 8400 Tstat Thermostat User Manual


 
15
SETUP & TESTING
System setting Setting range, default in bold
16LowBalancePt.(8446,8448HP,8465,8466HP)
Systemsetting05mustbeenabled
20°F (–7°C)
1°Fto35°F(–17°Cto1°C)or“OFF”todisable
17HighBalancePt.(8446,8448HP,8465,8466HP)
Systemsetting05mustbeenabled
60°F (16°C)
40°Fto80°F(4°Cto27°C)or“OFF“todisable
19Programformat(8463,8465,8466)
0 – 5/2 program (Weekdays and Weekends)
1–5/1/1program(Weekdays,Sat.andSun.)
20Changeairfilter
OFF
1,3,6,12monthsor“OFF”todisable
21Changewaterpanel**
Setnumberofmonthsuntilreminderisrequired
OFF
1to12monthsor“OFF”todisable
22Humidifiertype**
0 : Flow through type humidifier (1 reminder per season)
1:Drain-lesstypehumidifier(2 reminders per season)
23Servicedehumidifier
OFF
1to12monthsor“OFF”todisable
24ServiceHVAC
OFF
1to12monthsor“OFF”todisable
**IfhumidifiertypeissettoDrain-less,thenthefirstreminderisbasedonthesystemsetting21,secondreminder
willactivate3monthslater.IfhumidifiertypeissettoFlowthrough,thenthefirstreminderisbasedonsystem
setting21,secondreminderwillactivate12monthslater.