American Water Heater American Water Heaters Residential Gas Water Heater Water Heater User Manual


 
13
Figure 7. The water heater should have clearances of at least 1 inch
(25mm)fromthesidesandbackand6inches(150mm)fromthefront
of the appliance. The opening should directly communicate with the
outdoors or should communicate through a vertical or horizontal duct
to the outdoors or spaces that freely communicate with the outdoors
and should have a minimum free area of the following:
1. 1squareinchper3000Btu/hr(700mm
2
perkW)ofthetotalinput
rating of all appliances located in the enclosure, and
2. Not less than the sum of the areas of all vent connectors in space.
OUTDOOR AIR THROUGH TWO HORIZONTAL DUCTS
FIGURE 8.
Connedspaceshouldbeprovidedwithtwopermanenthorizontal
ducts,onecommencingwithin12inches(300mm)oftopandone
commencingwithin12inches(300mm)ofbottomofenclosure.Horizontal
ducts should communicate directly with outdoors. See Figure 8.
Each duct opening should have a minimum free area of 1 square inch
per2,000Btu/hr(1100mm
2
perkW)oftheaggregateinputratingofall
appliances installed in the enclosure.
When ducts are used, they should be of the same cross sectional area
as the free area of the openings to which they connect. The minimum
dimension of rectangular air ducts should be not less than 3 inches.
OUTDOOR AIR THROUGH TWO VERTICAL DUCTS
The illustrations shown in this section of the manual are a reference for
theopeningsthatprovidefreshairintoconnedspacesonly.
Do not refer to these illustrations for the purpose of vent installation.
See Installation of Vent System on pages 18-27 for complete venting
installation instructions.
FIGURE 9.
Theconnedspaceshouldbeprovidedwithtwopermanentvertical
ducts,onecommencingwithin12inches(300mm)ofthetopand
onecommencingwithin12inches(300mm)ofthebottomofthe
enclosure. The vertical ducts should communicate directly with the
outdoors. See Figure 9.
Each duct opening should have a minimum free area of 1 square inch
per4,000Btu/hr(550mm
2
perkW)oftheaggregateinputratingof
all appliances installed in the enclosure.
When ducts are used, they should be of the same cross sectional
area as the free area of the openings to which they connect. The
minimum dimension of rectangular air ducts should be not less than
3 inches.
AIR FROM OTHER INDOOR SPACES
FIGURE 9A.
The confined space should be provided with two permanent
openings,onecommencingwithin12inches(300mm)ofthetop
andonecommencingwithin12inches(300mm)ofthebottomof
the enclosure. See Figure 9A.
Eachopeningshouldcommunicatedirectlywithanadditionalroom(s)
ofsufcientvolumesothatthecombinedvolumeofallspacesmeets
thecriteriaforanUnconnedSpace.
Each opening should have a minimum free area of 1 square inch per
1,000Btu/hr(1100mm
2
perkW)oftheaggregateinputratingofall
appliances installed in the enclosure. Each opening should not be
lessthan100squareinches(645cm
2
).