ACTION:
To get to the current fault information screen, press Menu.
DISPLAY:
ACTION:
Press the DOWN button to highlight "current Fault" and press Select.
DISPLAY:
ACTION:
Press the DOWN button for more information.
DISPLAY:
7. Viewing the Fault History
The controller for this water heater will store a history of ten of the last Fault
and Warning conditions that occurred. This is stored in the Fault History.
Along with all the information about the fault, including a estimate time of
when the fault occurred, information regarding the advanced diagnostics for
that fault can be accessed at any time.
ACTION:
Press the DOWN button for more information.
DISPLAY:
ACTION:
Press the DOWN key to scroll through the fault history. If you select a
specic fault or warning, you may press the VIEW button to view details
regarding this fault.
DISPLAY:
8. Viewing Information About the Heater
The electronic control for this water heater monitors many different aspects
of the water to ensure safe and optimal operation. Much of the information
monitored is available to view in two areas of the control. The rst is the
"Heater Status" and; the second is "Heater Information." These items can be
selected through the main menu in the same fashion as described above.
In these menus, detailed information about the water heater and the current
status of specic conditions can be found.
INSTALLATION OR SERVICE OF THIS WATER HEATER REQUIRES
ABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN THE
FIELD INVOLVED. PLUMBING, AIR SUPPLY, VENTING, GAS SUPPLY
AND ELECTRICAL WORK ARE REQUIRED.
Before attempting start-up, thoroughly study and familiarize yourself with
the exact sequence of operation and all other details on the specic heater
being used.
The power burner is equipped with an ignition system which automatically
sequences prepurge and ignition, senses and ignites main burner ame and
sequences burner operation. Heater is equipped with an ignition control which
locks out after three unsuccessful ignition attempts. Familiarize yourself with
the sequence of operation of this unit prior to start-up.
Be certain that the water heater is full of water, that air is purged from all lines,
there are no leaks (gas and water), and all inlet water lines are open.
The following test equipment should be on hand (all test equipment must be
acclimated to ambient temperature before calibration and use.)
– Two U-tube manometers or calibrated pressure gages that can read
0-10" (0-2.5Kpa) and 0-35" (0-8.7Kpa) W.C. pressure gauges.
Attach a gas pressure gauge or manometer to the upstream side of
main gas cock and a gas pressure gauge or manometer to the manifold
pressure tap (see Figure 15).
You are now ready to begin the burner start-up procedure.
PRIOR TO START UP
REQUIRED ABILITY