American Sensor ASD100 Smoke Alarm User Manual


 
chamber. To avoid nuisance alarms, DO NOT place smoke alarms:
• In high humidity areas such as bathrooms and attics. Place smoke alarms at least 3 meters (10 feet) away from
bathrooms.
• In insect-infested areas.
• In poorly ventilated kitchens or garages.
• In very dusty and dirty areas.
• Near fluorescent lights. Place smoke alarms at least 1.5 meters (5 feet) from fluorescent lights.
This smoke alarm is suitable for residential use. It is not to be connected to a commercial or
industrial fire alarm panel.
6. INSTALLATION AND TESTING
A. Installation
Mount to any standard octagon or rectangular junction box with a minimum depth of 2.5 cm (1 inch).
12-24 Volt AC/DC, 145mAAC or 65mA DC operation
WARNING: Wiring should only be installed by a licensed electrician in accordance with the Canadian Electrical
Code and local codes.
WARNING: The circuit used to power the smoke alarm must be a 24 hour voltage circuit that cannot be turned off
by a switch or a ground fault interrupter. It is highly recommended that smoke alarms be wired on a separate circuit
(one with no other lights or appliances) to ensure maximum reliability of AC/DC power supply. For installation of
smoke alarms in Dwelling Units, it is important to follow the Canadian Electrical Code and local codes.
1. Electricity must be turned off at service entrance before beginning installation to prevent electrical shock or
equipment damage.
2. Location must comply with applicable building codes.
3. Install a junction box where you plan to install the alarm. Use standard 14 gauge wire.
4. Loosen or remove screws from junction box.
5. Pull the connection wires from the
junction box through the gasket
and the mounting plate. Using
the junction box screws secure
the gasket and the flat side of
mounting plate to the junction box
and ceiling or wall (ensure that
the gasket is positioned between
the mounting plate and the
junction box). The gasket will
prevent downward air currents
from entering the smoke alarm
through holes in the back of the alarm. Unless blocked off, downward air currents could prevent smoke from
entering the alarm. WARNING: IT IS IMPERATIVE THATYOU INSERT THE GASKET WHEN INSTALLING
YOUR SMOKE ALARM.
6. Connect black and red wires colour to colour from the unit to AC/DC power leads. If the units are powered from
a DC power supply, connect the RED wire to the postive (+) terminal and the BLACK wire to the negative (-)
terminal.
7. For multiple station application use the brown wire to interconnect. If unit is not to be interconnected, cap
unused wire. NOTE: The ASD100 is
interconnectable with up to 11 other
units.
8. Align the arrow on mounting plate with
the arrow on the side of smoke alarm
cover. Clips on the mounting plate
should fit into the recesses of smoke
alarm base. Twist the smoke alarm
clockwise to lock into position.
9. Test alarm operation after installation in accordance with “Operation: How to Test” instructions.
Model ASD100 provides one form C (NO/NC) contact
which activates on alarm. Contact rating (resistive): 1 A at
30V DC/125 VAC.
Relay wires (yellow/white/blue) 14 gauge stranded copper.
Install in accordance with Canadian Electrical code and
local building codes.
Note: Maximum interconnect wiring length is 50 meters
(150 feet).
IMPORTANT: The ASD100 is not interconnectable with any other model produced by another manufacturer.
The ASD100 may be interconnected only with the following smoke alarm models in existing installations.
Dicon Safety Products 330SR (construction identical with ASD100)
ASI Systems Devices ASD200, photoelectric
Dicon Safety Products 440SRIM, photoelectric (construction identical with ASD200)
To interconnect with models ASD200 or 440SRIM:
- Consult the ASD200/44SRIM installation manual.
- Ensure that all interconnected units are powered up from the same 12/24 V DC power supply, with the RED and
BLACK wires of the ASD100 connected to the positive (+) and negative (-) terminals, respectively.
- Connect the BROWN/interconnect wire of the ASD100/330SR to the positive (+) INTERCONNECT terminal of the
ASD200/440SRIM.
Terminal blocks accept wire between 18-22 AWG. Read ASD200 owner’s manual.
For a more complete discussion of installation and location requirements refer also to: CAN/ULC-S553-02 “Standard for the
Installation of Smoke Alarms” (available from Underwriters Laboratories of Canada, 7 Crouse Road, Scarborough, Ontario M1R
3A9).
B. Operation: Testing After Installation
1. Smoke Test - Hold a piece of cotton string with pliers. Leave about 5 cm (2 inches)of string dangling from the
pliers. Burn the tip of the string with a safety match, extinguish flame and hold smoking string 15 cm (6 inches)
below and to one side of the smoke alarm. Blow smoke towards the smoke alarm until the horn sounds. The
horn will sound until the sensing chamber is clear of smoke. Repeat this monthly.
2. Check to see that the RED “POWER ON” light is on. The “POWER ON” light is visible behind the slotted case
and confirms that the smoke alarm is receiving AC/DC power.
3. Press and hold the test button until the alarm sounds. NOTE: It may be necessary to press the test button for
up to 20 seconds for alarm to sound. An alarm is indicated by a loud pulsating sound. Alarm may continue to
sound for up to 10 seconds after button is released. (NOTE: Pressing the test button activates the relay.)
4. At least once a week, press the test button and hold until the alarm sounds, then release.
NOTE: Multiple Station Only:
5. Test each alarm separately in the system.
6. Determine that the initiating alarm triggers other alarms in the system.
NOTE: Pressing the test button activates the relay.
SMOKE ALARM MANUAL
Ionization Type with Built-in Relay
Model ASD100 - 12/24 Volt AC/DC Hardwire Smoke Alarm.
This model is interconnectable with up to 11 other units.
Important information about your smoke alarm
• Install alarms outside of every bedroom area and on every floor of your home. Please refer to Section 3 “Where
to Locate Smoke Alarms” for details.
Test the alarm weekly by pressing and holding the test button for up to 20 seconds until the alarm sounds.
The model described in this manual is designed for single family residences, including homes and apartments
rather than commercial or industrial use.
Smoke Alarm Safety Features
Dual-Ionization Chambers - Advanced design responds to visible or invisible particles of combustion (smoke) to
sense fires in the early stages. Compensates for changes in humidity and temperature to virtually eliminate
“nuisance” alarms caused by normal atmospheric changes in the home.
Operating Light (LED) - A continuous red light located behind the slotted case indicates the smoke alarm is
receiving AC/DC power.
Interconnection - Interconnection facilities for up to 11 other units, using only three wires, including AC/DC power.
When one alarm sounds, all properly interconnected smoke alarms follow. NOTE: Interconnect only with the
models specified in Section 6.
Alarm Source Indicator - The red operating light in the unit originating the alarm will flash rapidly in the event of
an alarm. This feature allows for an easy check to determine the originator.
Sensitivity Test Button - Test sensitivity, as well as circuitry and horn. With interconnected units, activating test
button on one unit will cause all properly interconnected units to sound. An important and convenient check of
system integrity.
Detachable Mounting Plate - For easily securing the alarm to the junction box.
MAXIMUM POWER REQUIREMENT
OPERATING VOLTAGE 12/24 Volts AC or DC
from a ULC Listed Power Supply or a
Residential Fire or Fire/Burglary Alarm Control Unit.
Supply Standby (mA) Alarm (mA)
DC 50 65
AC 50 145
Relay Connection- Provides one Form C, normally open/normally closed contact which is activated on alarm.
CONTENTS OF THIS MANUAL
1. CAPABILITIES AND LIMITATIONS OF SMOKE ALARMS
2. SAFETY TIPS
3. WHERE TO LOCATE SMOKE ALARMS
4. NFPARECOMMENDATIONS
5. LOCATIONS TO AVOID
6. INSTALLATION AND TESTING
7. MAINTENANCE AND TROUBLESHOOTING
8. LIMITED WARRANTY
1. CAPABILITIES AND LIMITATIONS OF SMOKE ALARMS
American Sensors smoke alarms are designed to provide early warning of fire and smoke at reasonable cost. Early
warning can mean the difference between a safe escape and no escape at all. While smoke alarms can provide
invaluable protection for you and your family, they do have limitations.
• Smoke alarms cannot work without power. Battery operated alarms will not work without proper batteries, with
dead batteries or if batteries are not properly installed. AC/DC powered alarms will not work if their AC/DC power
supply is cut off by an electrical fire, an open fuse, a circuit breaker or any other reason.
If you are concerned about the reliability of either battery or your AC/DC power supply for any of the above
reasons, you should install in your home both AC and battery powered smoke alarms for added security.
• Smoke alarms are incapable of sounding the alarm until smoke reaches the sensing chamber. Anything
preventing smoke from reaching the alarm may delay or prevent an alarm. A smoke alarm cannot detect fire in
the walls, chimney or roof unless and until a significant amount of smoke reaches the alarm. A closed door may
prevent smoke from reaching an alarm on the other side of the door. A smoke alarm may not sense a fire on
another floor of a home. For example, a basement smoke alarm may not detect a fire which started on the first
or second floor.
• Smoke alarms may not be heard. The loudness of the horn in your alarm meets current standards. However, the
sound may be blocked by distance, closed doors, or ambient noise such as traffic or a stereo. Smoke alarms
may not be heard by persons who are hard of hearing.
For these reasons, a smoke alarm should be installed in every room or at least on every level of your home.
American Sensors Inc. recommends that hardwire AC/DC Powered smoke alarms be interconnected, so that one
alarm will trigger all other alarms to sound.
• Smoke alarms are not fool-proof. Smoke alarms may not always sense every kind of fire. They cannot be
expected to sense fires caused by carelessness or by safety hazards. They may not give early warning of fast
growing fires caused by careless smoking, violent explosions, escaping gas, improper storage of flammable
materials, overloaded electrical circuits, natural causes such as lightning, children playing with matches, or arson.
• Smoke alarms are not substitutes for property, disability, life or other insurance of any kind. Home owners and
renters should continue to insure their lives and property. Consult your insurance agent.
• Smoke alarms have limited lives. Your smoke alarm should be replaced if it is ten years old. One or more of
the many components could fail at any time. Therefore, test your smoke alarm weekly. Clean and take care of it
as described in this manual. Repair or replace the smoke alarm when it fails to test properly.
Ionization Technology vs.
Photoelectronic Technology
Smoke Alarms
2. SAFETY TIPS
Properly installed and maintained smoke alarms are an essential part of a good home fire safety program. Your fire
safety program should also include a review of fire hazards and the elimination of dangerous conditions whenever
possible. Consider the following tips:
• Use smoking materials properly. Never smoke in bed.
• Keep matches and cigarette lighters away from children.
• Store flammable materials in proper containers. Never use them near an open flame or sparks.
• Keep electrical appliances in good condition. Do not overload electrical circuits.
• Keep stoves, fireplaces, chimneys, and barbecue grills grease free. Make sure they are properly installed and
away from any combustible materials.
• Keep portable heaters and open flames such as candles away from combustible material.
• Do not allow rubbish to accumulate.
• Keep a supply of extra batteries on hand for your battery powered smoke alarms.
• Do not stand too close to the alarm when the unit is in alarm as the loud horn could damage your hearing.
Never disconnect the battery or the AC/DC power on any type of smoke alarm to silence a
nuisance alarm. Clear the area of smoke by opening doors and windows or fanning the
smoke away.
Most important, when fire strikes, a prepared and practiced escape plan can make the difference between life and
death. Develop an escape plan and practice it with the entire family, including small children.
• Ensure all family members are familiarized with the alarm signal.
• Prepare an escape plan. Draw a Floor Plan of Your Home and determine two exits from each room. There
should be a way to get out of each bedroom without opening the door.
• Have Fire Drills Often. Practice your Escape and BE PREPARED.
• Decide on a meeting place at a safe distance from your home.
IN CASE OF FIRE
• Don’t waste time collecting possessions after a fire starts.
• Arouse all occupants and leave the building. Your most valuable possession is your life.
• Doors can mean escape or death. Never open doors without first checking for heat. Test them with your hands, if
they feel warm, fire may be walled up behind them - leave closed and find another escape route.
• Call the fire department from OUTSIDE the building.
• If trapped inside, stay close to the floor, cover mouth with cloth, conserve breath as you crawl to safety.
• Keep all doors and windows closed except for escape purposes.
• NEVER re-enter a burning building.
• Keep your family in a pre-arranged meeting place after your escape.
Your local fire department may be able to offer you additional ideas for safety and escape plans in the home.
3a. WHERE TO LOCATE SMOKE ALARMS
As a minimum, smoke alarms should be located between sleeping areas and potential sources of fire such as a
kitchen, heated garage or basement. In single storey homes with one sleeping area, an alarm should be installed
in the hallway outside the bedrooms (see Figure 1). In single storey homes with two separate sleeping areas, a
minimum of two alarms are required, one outside each sleeping area (see Figure 2). In multi-level or split-level
homes, as a minimum, an alarm should be installed outside each sleeping area, in the basement and at every level
of the home (see Figure 3).
• In every room of your home (except the bathroom): Research indicates that substantial increases in warning time
can be obtained with each properly installed, additional alarm.
• In bedrooms: In anticipation of fires originating within these rooms, caused by faulty wiring, lamps, appliances,
smoking or other hazards.
• In hallways: At a distance no greater than 4 meters (13 feet) from the farthest wall and no greater than 8 meters
(26 feet) from the next alarm.
• In the center of a room or hallway: As it is impossible to predict the source of a fire. If it is necessary to place the
alarm on a wall, always locate the top of the smoke alarm 10-15 cm (4-6 inches) from the ceiling.
• As needed: To compensate for closed doors and other obstacles that may interfere with the path of smoke to an
alarm. They may also prevent occupants on one side of a closed door from hearing an alarm on the other side
of the door.
• Model ASD100 - Hardwire model can be located in any area of the home, except the bathroom.
READ “CAPABILITIES AND LIMITATIONS OF SMOKE ALARMS” in Section 1 of this manual.
Your local fire department or insurance company may be able to give you further advice on the best smoke alarm
locations in your home. Call them and ask.
3b. WHERE TO LOCATE SMOKE ALARMS IN MOBILE HOMES.
NOTE: Power supply must be 12/24 Volts AC/DC for model ASD100.
In mobile homes built after 1978, locate the smoke alarm as described above. Older mobile homes may have little
or no insulation compared to the ones built post-1978. These uninsulated exteriors can disrupt airflow around the
smoke alarm in hotter or colder weather. Locate the alarm only on interior walls 10 to 15 cm (4” to 6”) from ceiling
1. if you own an older mobile home, or 2. if you notice the exterior walls and/or ceiling are noticeably cold or warm
or 3. if you are uncertain about the quality of insulation.
Regardless of the age of the mobile home, locate alarms throughout to ensure maximum protection. Follow the
location instructions in this manual.
4. NFPA RECOMMENDATIONS
For your information, the National Fire Protection Association’s Standard 72, reads as follows:
2-2.1.1.1 Smoke alarms shall be installed outside of each separate sleeping area in the immediate vicinity of the
bedrooms and on each additional storey of the family living unit, including basements and excluding
crawl spaces and unfinished attics. In new construction a smoke alarm also shall be installed in each
sleeping room.
A-2.5.2.1 Smote Detection - Are More Smoke Alarms Desirable? The required number of smoke alarms might
not provide reliable early warning protection for those areas separated by a door from the areas
protected by the required smoke alarms. For this reason, it is recommended that the householder
consider the use of additional smoke alarms for those areas for increased protection. The
additional areas include the basement, bedrooms, dining room, furnace room, utility room, and
hallways not protected by the required smoke alarms. The installation of smoke alarms in kitchens,
attics, (finished or unfinished), or garages is not normally recommended, as these locations
occasionally experience conditions that can result in improper operation.
5. LOCATIONS TO AVOID
Avoid locations where smoke may not reach the alarm in time to provide early warning, or where the alarm may not
be effective.
DO NOT PLACE SMOKE ALARMS:
• In turbulent air from fans, doors, windows, etc. The rapid air movement may prevent combustion particles from
entering the alarm.
• In dead air spaces such as at the peak of an “A” frame ceiling. “Dead air” at the top may prevent smoke from
reaching the alarm in time to provide early warning. In rooms with simple sloped, peaked or gabled ceilings,
install smoke alarms on the ceiling
90 cm (3 feet) from the highest point of the ceiling.
Note: For complex ceiling structures, consult a safety expert for the number of alarms required and the best
locations.
• In very hot or cold areas where the temperature exceeds 38
0
C (100
0
F) or falls below 5
0
C (40
0
F).
• Less than 15 cm (6 inches) from the wall when mounted on the ceiling.
Nuisance alarms could result when smoke alarms are located where interference may occur with the sensing
Owner’s Manual
Manuel de l'utilisateur
READ CAREFULLY AND SAVE.
This manual contains important information.
A copy of this manual must be left with the end user.
LIRE ATTENTIVEMENT ET CONSERVER CE MANUEL.
Le présent manuel renferme des renseignements
importants. Un exemplaire de ce manuel doit être
remis à l'utilisateur final.
(French on reverse/Français au verso)
2502-2522REVA
REPLACEMENT OF SMOKE ALARMS AFTER 10 YEARS OF SERVICE
Smoke alarms contain electronic parts that may fail and components that can deteriorate over time. Therefore,
smoke alarms have a limited service life. See the replacement year printed on the side of the alarm.
7. MAINTENANCE & TROUBLESHOOTING
TEST THE ALARM WEEKLY. VACUUM EVERY SIX MONTHS.
Your smoke alarm should be cleaned every six months to help keep the unit working efficiently. REMOVE POWER
TO ALARM. Gently vacuum through the vents of the alarm with a soft brush attachment. Keep vacuum nozzle
from touching the unit.
RE-ESTABLISH POWER TO ALARM.
Problems may be indicated by the following:
1. The alarm does not sound upon pressing the test button.
2. The alarm does not sound with the smoke test.
3. The RED operating light does not remain steadily on when unit is powered.
TRY THE FOLLOWING:
1. Ensure power supply is within the specified parameters and all fuses/circuit breakers are intact.
2. Gently vacuum as recommended above.
3. Call an electrician to inspect house wiring and connection to alarms.
If these procedures do not correct the problem, do NOT attempt repairs. If the smoke alarm is within warranty
period and terms, indicate the nature of the problem and return the unit with proof of purchase to the point of
purchase, distributor or manufacturer. See below for instructions. Units beyond warranty cannot be economically
repaired.
FALSE ALARMS:
Abnormal air conditions may cause the highly sensitive smoke alarm to give a “false” alarm. If no fire is apparent,
ventilate the room and/or blow fresh air into the unit until the alarm stops. Once cleared, the smoke alarm will
automatically reset.
DO NOT DISCONNECT THE AC/DC POWER SUPPLY.
Dust can lead to excess sensitivity. Vacuum as recommended above.
DO NOT PAINTTHE UNIT.
Smoke alarms contain electronic parts that may fail and components that can deteriorate over time. Therefore,
smoke alarms have a limited service life. In order to prolong the service life and to provide optimal performance,
smoke alarms should be tested and cleaned periodically. It is strongly recommended that smoke alarms be
replaced within 10 years of original installation.
8. LIMITED WARRANTY
Your American Sensors smoke alarm is warranted for ten years from the date of purchase against defect in
material and workmanship. Units returned to Dicon Global Inc. with proof of purchase date during this period as a
result of such defects will be repaired, or replaced at Dicon Global Inc.’s option. This warranty only covers defects
in material or workmanship in normal residential use. This warranty does not cover damage resulting from
negligent handling, misuse, or lack of reasonable care. This warranty is in lieu of any other warranty either
expressed or implied.
DICON GLOBAL INC. SHALLHAVE NO LIABILITY FOR ANY PERSONAL INJURY OR PROPERTY DAMAGE,
OR ANY SPECIAL INCIDENTAL, CONTINGENTOR CONSEQUENTIAL DAMAGE OF ANY KIND RESULTING
FROM A FIRE. THE EXCLUSIVE REMEDY FOR BREACH OF THE LIMITED WARRANTY CONTAINED
HEREIN IS THE REPAIR OR REPLACEMENT OF THE DEFECTIVE PRODUCT AT DICON GLOBAL INC.’S
OPTION. IN NO CASE SHALL DICON GLOBALINC.’S LIABILITY UNDER ANY OTHER REMEDY
PRESCRIBED BY LAW EXCEED THE PURCHASE PRICE. YOUR SMOKE ALARM IS NOTA SUBSTITUTE
FOR PROPERTY, DISABILITY, LIFE OR OTHER INSURANCE OF ANY KIND. APPROPRIATE COVERAGE IS
YOUR RESPONSIBILITY. CONSULT YOUR INSURANCE AGENT.
This warranty gives you specific legal rights and you may have other rights which may vary from Province to
Province.
Return to point of purchase for servicing. Or, for repair or replacement within the warranty period, return this
product (or send it postage prepaid) along with proof of purchase date to Dicon Global Inc. Please enclose a note
stating the nature of the difficulty. Prior to sending, please call our toll free 1-800 line (1-800-387-4219) to
establish a Returned Goods Authorization (“RGA”) number and the latest instructions to serve you promptly.
Please mark this number on the exterior of your package. Note: Date code located on back of unit.
Dicon Global Inc.
20 Steelcase Road West, Unit #3
Markham, Ontario, Canada L3R 1B2
1-800-387-4219
www.diconglobal.com
WARNING
!
WARNING
!
Kitchen
Living
Room
BedroomBedroom
Basement
Hall
Hall
Furnace
Figure 1
Figure 2
Figure 3
Smoke alarms for limited protection
Additional smoke alarms for better coverage
These diagrams show smoke alarm locations as recommended
above in 3a.
BLACK (-)
RED (+)
YELLOW
WHITE
BLUE
BROWN
12-24V AC OR DC
NORMALLY CLOSED
NORMALLY OPEN
COMMON
INTERCONNECT
Smoke alarm
paper gasket
mounting plate
Mounting
plate
Smoke alarm
BLACK (-)
12-24V AC OR DC
RED(+)
Cap Unused Wire
Twist Connectors
Ceiling
Supplied Gasket Must Be Installed between
Outlet Box and Mounting Plate
Mounting Plate
BLACK (-)
12-24V AC OR DC
RED (+)
BROWN Interconnect
MODELASD100
12/24 Volt AC/DC Ionization
Interconnectable Smoke Alarm
MULTIPLE STATION
Smoke Alarm
Outlet Box
SINGLE STATION
There are two different types of smoke alarm technology currently in general use: Ionization and
photoelectronic. While both types of technology are suitable for general residential use, an ionization alarm will
normally respond faster to fast flaming fires, while a photoelectronic alarm may be more sensitive to detecting
slow smouldering fires. Because home fires develop in different ways and are often unpredictable in their
growth, it is impossible to predict which type of alarm will provide the earliest warning. For best home protection
install at least one photoelectronic and one ionization smoke alarm on each level of your home. Model ASD100
is an ionization type smoke alarm. A photoelectronic smoke alarm senses smoke using an electronic photo
receptor to sense the scattering of light by smoke particles. Model ASD200 is a photoelectric smike alarm
interconnectable with model ASD100.
RELAY CONNECTION
MODEL/MODÉLE
ASD100
12-24V AC/DC Ionization
Smoke Alarm with Built-In Relay
AVERTISSEUR DE FUMÉE
À IONISATION
avec Relais
c.a/c.c.12-24 V
25022522REVA ASD100 man.-CAN.qxp 12/14/2006 9:46 AM Page 1